03.06.2013 Views

1 - page screenshot of chlodzenie.pl

1 - page screenshot of chlodzenie.pl

1 - page screenshot of chlodzenie.pl

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

5CSL0-06B<br />

2.3.3 Grouped drain pipes<br />

NOTE<br />

It is standard work practice to make connections to the main pipe from above.<br />

The pipe down from the combination should be as large as possible.<br />

The diameter <strong>of</strong> ventilation pipe should be same or larger than drain pipe diameter.<br />

45~60°<br />

45~60°<br />

45~60°<br />

Grouped drain piping standard<br />

slope 1/50 ~ 1/100<br />

45~60° angle connection against overflow<br />

Sharing horizontal pipe<br />

700mm<br />

maxinmum<br />

Common drain pipe<br />

Trap in the end<br />

Drain piping work<br />

Face the vent pipe mouth<br />

downward to keep foreign matter<br />

from penentrating the system<br />

1. Trap is required if the pie is open towards sewage to prevent bad smell from coming to indoor.<br />

2. Do not connect drain pipe with building common drain pipe in heavy snow area. It might block the pipe with ice and<br />

remaining collected water can get back to indoor unit.<br />

Provide seperate air conditioner drain pipe.<br />

- For drain pipe diameter selection, refer to the following table.<br />

- The drainpipe should be used for only air conditioners. If you share it for rainwater drain, you should be careful <strong>of</strong> a<br />

back flow, leakage, bad odor and so on.<br />

- Use separate drain pipe for polluted water or wasted water<br />

NOTE<br />

Sum <strong>of</strong> the capacity<br />

<strong>of</strong> indoor units (Btu/h)<br />

[Table] Drain pipe diameter selection standard<br />

~80,000 ~200,000 ~400,000 ~600,000 ~1000,000<br />

Internal diameter (External) 25(32) 32(40) 40(50) 50(60) 65(75)<br />

Select the diameter <strong>of</strong> the horizontal pipe bigger than vertical.<br />

Guideline for each installation process 301

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!