5CSL0-06B<br />

2.3 Non inverter Single A (1Ø, 3Ø)<br />

2.3.1 Power sup<strong>pl</strong>y<br />

External wiring procedure<br />

Power sup<strong>pl</strong>y<br />

Type Outdoor unit Capacity (kW) Circuit breaker capacity Power sup<strong>pl</strong>y<br />

AUUH126D[UU12 ULD]<br />

AUUH186D[UU18 UED]<br />

AUUH246D[UU24 UED]<br />

3.5<br />

5.0<br />

7.1<br />

15A<br />

20A<br />

1Ø, 220-240 V, 50Hz<br />

Heat pump AUUH306D[UU30 UED] 8.0 30A<br />

AUUH368D[UU37 UED] 10.0 25A<br />

AUUH488D[UU48 U3D] 14.0 30A 3Ø, 380V-415V, 50Hz<br />

AUUH608D[UU60 U3D] 15.0 30A<br />

- The power sup<strong>pl</strong>y work is needed only to the outdoor unit. The power sup<strong>pl</strong>y to the indoor unit is conducted through the<br />

transmission wiring.<br />

- Wiring cable size must com<strong>pl</strong>y with the ap<strong>pl</strong>icable local and national code.<br />

Circuit breaker<br />

Power sup<strong>pl</strong>y<br />

Earth<br />

Outdoor unit<br />

Outdoor unit - Non inverter Single A (1Ø, 3Ø) 245