Electric characteristics<br />

2.3.10 Electric characteristics<br />

Outdoor Unit<br />

Power Compressor OFM<br />

5CSL0-06B<br />

Model Type Hz Voltage Voltage range MCA MOP MSC RLA kW FLA<br />

AUUH126D<br />

[UU12 ULD]<br />

AUUH186D<br />

[UU18 UED]<br />

AUUH246D<br />

[UU24 UED]<br />

AUUH306D<br />

[UU30 UED]<br />

AUUH368D<br />

[UU37 UED]<br />

AUUH488D<br />

[UU48 U3D]<br />

AUUH608D<br />

[UU60 U3D]<br />

Non inverter 50<br />

220-240<br />

380-415<br />

Notes :<br />

1. Voltage range<br />

Voltage sup<strong>pl</strong>ied to the unit terminals should be within the<br />

minimum and maximum range<br />

2. Maximum allowable voltage unbalance between phase is 2 %<br />

3. MCA / MOP<br />

MCA = (1.25 x Load1) + Load2 + Load3<br />

MOP = (2.25 x Load1) + Load2 + Load3<br />

- Load1 : Rated running current <strong>of</strong> largest motor<br />

(compressor or other motor)<br />

- Load2 : sum <strong>of</strong> current for all other motors<br />

- Load3 : any other load rated 1.0A or more<br />

4. Select wire spec. based on the MCA<br />

5. Recommended circuit breaker is ELCB (Earth Leakage circuit<br />

breaker)<br />

6. MSC & RLA are measured as the compressor only test<br />

condition.<br />

7. MSC values<br />

Min.: 198<br />

Max.: 264<br />

Min : 352<br />

Maxi :457<br />

7.50 13.50 24.00 6.00 0.10 0.51<br />

11.25 20.25 35.00 9.00 0.13 0.70<br />

13.75 24.75 62.00 11.00 0.13 0.70<br />

20.88 37.58 82.00 16.70 0.13 0.70<br />

9.13 15.63 47.00 6.50 0.16 1.00<br />

12.77 22.07 63.00 9.30 0.25 1.14<br />

13.14 22.74 74.00 9.60 0.25 1.14<br />

8. RLA is measured during each individual compressor test<br />

condition.<br />

9. OFM is measured as the outdoor unit test condition<br />

(Exam<strong>pl</strong>e) Selection <strong>of</strong> proper circuit breaker<br />

① Model : AUUH126D[UU12 ULD]<br />

- Rated running current : 6.0A (refer to spec. sheet)<br />

② MCA = (1.25 x Load1) + Load2 + Load3<br />

= (1.25 x 6.0) + 0 + 0 = 7.5A<br />

③ MOP = (2.25 x Load1) + Load2 + Load3<br />

= (2.25 x 6.0) + 0 + 0 = 13.5A<br />

→ Finally select circuit breaker 15A (Min. circuit breaker is 15A)<br />

MCA : Minimum Circuit Amperes (A)<br />

MOP : Maximum rating over current protective device<br />

MSC : Maximum Starting Current<br />

RLA : Rated Load Amperes (A)<br />

OFM : Outdoor Fan Motor<br />

kW : Fan Motor rated output (kW)<br />

FLA : Full Load Amperes (A)<br />

284 Outdoor unit - Non inverter Single A (1Ø, 3Ø)