Refrigerant piping work 5CSL0-06B<br />

2.2 Refrigerant piping work<br />

2.2.1 Flaring work<br />

NOTE<br />

CAUTION<br />

Flare connection and procedure<br />

1. Stiffened pipe must always be annealed at least once<br />

prior to the flaring work.<br />

A<br />

2. A pipe cutter must be used to cut the pipe.<br />

(A large pipe cutter must be used where<br />

the pipe has a large diameter. When cutting<br />

a pipe which is too big for the pipe cutter a<br />

metal saw may be used but care must be<br />

taken to ensure that the debris from sawing<br />

does not get into the pipe.)<br />

D<br />

CAUTION<br />

Choice <strong>of</strong> material for refrigerant piping<br />

Copper pipe selection<br />

a. The wall thickness <strong>of</strong> the refrigerant piping should com<strong>pl</strong>y with relevant local and national regulation for<br />

R410A the design pressure is 3.8MPa.(38.7kgf/cm2 )<br />

b. If not, we recommend to use with phosphorus deoxidized copper type<br />

c. Generally used copper pipe specifications as follows;<br />

Size(ø)mm<br />

Torque<br />

kg·f.m R22<br />

Thickness<br />

R410A<br />

6.35 1.80~2.50 0.7 0.8<br />

9.52 3.40~4.20 0.8 0.8<br />

12.70 5.50~6.60 0.8 0.8<br />

15.88 6.30~8.20 1.0 1.0<br />

19.05 9.90~12.1 1.0 1.0<br />

* Never use the pipe which is mixed scrap or a pipe used somewhere else<br />

The method how to distinguish the pipe mixed scarp : check the oxidization evidence after leaving the pipe for 24hour.<br />

External diameter <strong>of</strong> pipe D<br />

(in) (mm)<br />

1. Burrs should be carefully removed.<br />

2. 2 spanners should be used to grip the pipe.<br />

3. The flare nut must be inserted before starting the flaring operation.<br />

4. The appropriate amount <strong>of</strong> torque should be used to tighten the flare nut.<br />

5. Check that there is no superficial damage to the surface <strong>of</strong> the flare.<br />

H<br />

3. Set the flaring tool to make sure the flare size remains<br />

within the prescribed limits.<br />

4. Coat the inner and outer surface <strong>of</strong> the<br />

flare with refrigerator oil (Ester or ether<br />

oil).<br />

(this ensures that the flare nut passes<br />

smoothly, preventing the pipe Oil<br />

Oil<br />

from twisting.)<br />

Do not use SUNISO-4GS oil.<br />

Pipe widening dimension A<br />

(mm)<br />

Required flare height H<br />

(mm)<br />

1/4 6.35 8.6~9.0 1.1~1.3<br />

3/8 9.52 12.6~13.0 1.5~1.7<br />

1/2 12.7 15.8~16.2 1.6~1.8<br />

5/8 15.88 19.0~19.4 1.6~1.8<br />

3/4 19.05 22.9~23.3 1.9~2.1<br />

292 Guideline for each installation process