5CSL0-06B The coefficient <strong>of</strong> capacity change<br />

2.3.8 The coefficient <strong>of</strong> capacity change<br />

1) Rate <strong>of</strong> change in capacity due to the main piping length<br />

Rate <strong>of</strong> change in cooling capacity<br />

Main piping length(m)<br />

Rate <strong>of</strong> change<br />

in capacity(%)<br />

10 15 20 30 35 40 45 50<br />

3.5kW 99.2 97.6 - - - - - -<br />

5.0/6.0kW 99.5 98.4 97.4 95.2 94.2 93.1 - -<br />

7.1kW 99.7 99.1 98.5 97.4 96.2 95.8 94.3 92.0<br />

8.0kW 99.8 99.5 98.4 97.4 96.3 95.2 94.1 93.1<br />

14.0/15.0kW 99.5 98.4 97.4 95.2 94.2 93.1 92.1 91.0<br />

Rate <strong>of</strong> change in heating capacity<br />

Main piping length(m)<br />

10 15 20 30 35 40 45 50<br />

3.5kW 98.8 96.4 - - - - - -<br />

Rate <strong>of</strong> change<br />

in capacity(%)<br />

5.0/6.0kW<br />

7.1kW<br />

8.0kW<br />

99.5<br />

99.7<br />

99.5<br />

98.4<br />

99.1<br />

98.4<br />

97.4<br />

98.5<br />

97.4<br />

95.2<br />

97.4<br />

95.2<br />

94.2<br />

96.8<br />

94.2<br />

93.1<br />

95.2<br />

93.1<br />

-<br />

94.3<br />

92.1<br />

-<br />

91.8<br />

91.1<br />

14.0/15.0kW 99.5 98.4 97.4 95.2 94.2 93.1 92.1 91.0<br />

Outdoor unit - Non inverter Single A (1Ø, 3Ø) 281

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!