5CSL0-06B<br />

Models : AUUW246DH + ATNH24GNLED<br />

[UU24WH U4D] + [UT24 NND]<br />

• Cooling Capacity<br />

Model ATNH24GPLED[UT24 NND]<br />

AFR 21<br />

Capacity tables<br />

• Symbol<br />

AFR : Air flow rate [m3 Indoor Air<br />

Outdoor Air Temperature : °CDB<br />

Temperature 20 25 32 35 40 43 46<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 8.24 7.78 1.43 7.88 7.53 1.50 7.40 7.23 2.01 7.17 6.98 2.24 6.86 6.77 2.46 6.67 6.53 2.41 6.48 6.33 2.16<br />

16.0 22.0 8.74 7.89 1.94 8.38 7.65 1.96 7.90 7.37 2.37 7.67 7.13 2.54 7.36 6.93 2.65 7.17 6.70 2.52 6.98 6.51 2.19<br />

18.0 25.0 9.25 7.95 2.10 8.89 7.73 2.11 8.40 7.47 2.49 8.17 7.24 2.59 7.86 7.06 2.69 7.67 6.84 2.52 7.48 6.65 2.14<br />

19.0 27.0 9.50 8.02 2.12 9.14 7.81 2.14 8.65 7.55 2.51 8.40 7.31 2.59 8.11 7.15 2.70 7.92 6.93 2.51 7.73 6.75 2.12<br />

22.0 30.0 10.26 8.18 2.12 9.90 7.98 2.18 9.41 7.75 2.57 9.17 7.53 2.72 8.86 7.38 2.74 8.67 7.16 2.54 8.48 6.99 2.12<br />

24.0 32.0 10.77 8.34 2.11 10.40 8.14 2.20 9.91 7.93 2.62 9.67 7.71 2.77 9.36 7.56 2.80 9.17 7.35 2.60 8.98 7.18 2.17<br />

• Notes<br />

/min] 1. All capacites are net, evaporator fan motor heat is<br />

DB : Dry bulb temperature [°C]<br />

deducted.<br />

WB : Wet bulb temperature [°C] 2. Indicates rated capacity.<br />

TC : Total capacity [kW] 3. Direct interpolation is permissible. Do not extrapolate<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

• Heating Capacity<br />

Model ATNH24GPLED[UT24 NND]<br />

AFR 21<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 6.69 3.10 7.14 3.16 7.98 3.00 8.77 2.80 9.56 2.64 10.18 2.57 10.45 2.44<br />

18 6.63 3.15 7.13 3.23 7.99 3.09 8.77 2.88 9.49 2.71 10.05 2.63 10.42 2.47<br />

20 6.58 3.20 7.13 3.31 7.99 3.17 8.74 2.95 9.40 2.76 9.98 2.66 10.43 2.48<br />

21 6.56 3.23 7.13 3.36 7.99 3.22 8.72 2.99 9.34 2.79 9.98 2.68 10.37 2.49<br />

22 6.55 3.27 7.13 3.41 7.99 3.26 8.70 3.03 9.27 2.81 9.97 2.70 10.28 2.49<br />

24 6.49 3.32 7.06 3.46 7.89 3.30 8.65 3.06 9.26 2.83 9.81 2.70 10.22 2.50<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 205