Capacity tables 5CSL0-06B<br />

Models : AUUW216DH + ATNH21GNLED<br />

[UU21WH U4D] + [UT21 NND]<br />

• Cooling Capacity<br />

Model ATNH21GNLED[UT21 NND]<br />

AFR 19<br />

Indoor Air<br />

Temperature<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Heating Capacity<br />

Model ATNH21GNLED[UT21 NND]<br />

AFR 19<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 7.84 7.10 1.38 7.50 6.87 1.44 7.04 6.59 1.93 6.83 6.37 2.16 6.53 6.18 2.37 6.35 5.96 2.32<br />

16.0 22.0 8.33 7.19 1.87 7.98 6.98 1.89 7.52 6.72 2.28 7.31 6.50 2.45 7.01 6.32 2.55 6.83 6.11 2.43<br />

18.0 25.0 8.81 7.26 2.02 8.46 7.05 2.03 8.00 6.81 2.39 7.78 6.60 2.50 7.48 6.44 2.59 7.30 6.24 2.43<br />

19.0 27.0 9.05 7.32 2.04 8.70 7.12 2.06 8.24 6.89 2.42 8.00 6.67 2.50 7.72 6.52 2.60 7.54 6.32 2.42<br />

22.0 30.0 9.78 7.47 2.04 9.43 7.28 2.10 8.96 7.07 2.48 8.73 6.87 2.62 8.43 6.73 2.64 8.25 6.53 2.44<br />

24.0 32.0 10.26 7.60 2.03 9.91 7.43 2.12 9.44 7.23 2.52 9.21 7.03 2.67 8.91 6.90 2.69 8.73 6.71 2.50<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 6.40 2.89 6.84 2.94 7.64 2.79 8.40 2.61 9.15 2.46 9.75 2.40 10.01 2.28<br />

18 6.34 2.93 6.83 3.01 7.65 2.88 8.39 2.68 9.09 2.52 9.62 2.45 9.97 2.31<br />

20 6.30 2.98 6.83 3.09 7.65 2.96 8.37 2.75 9.00 2.57 9.56 2.48 9.99 2.32<br />

21 6.28 3.01 6.83 3.13 7.65 3.00 8.35 2.79 8.94 2.60 9.56 2.50 9.93 2.32<br />

22 6.27 3.05 6.83 3.18 7.65 3.04 8.33 2.82 8.88 2.62 9.55 2.51 9.85 2.32<br />

24 6.21 3.10 6.76 3.22 7.56 3.08 8.28 2.85 8.87 2.64 9.39 2.52 9.79 2.33<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

TC SHC PI<br />

6.17 5.77 2.08<br />

6.65 5.94 2.11<br />

7.12 6.06 2.06<br />

7.36 6.15 2.04<br />

8.07 6.37 2.04<br />

8.55 6.55 2.09<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />