5CSL0-06B<br />

5. Location free from electrical noise.<br />

6. Location allowing optimum air distribution without any<br />

blocking to air flow.<br />

7. Location having no risk <strong>of</strong> flammable gas leakage.<br />

8. Location free from mineral oil mist or an oil spray or vapor<br />

eg in kitchen .It could result in leakage .<br />

9. Location free from corrosive gases such as sulphurous<br />

acid gas because it corrodes the copper pipes or soldered<br />

parts resulting in leakage .<br />

10. Location free from any machinery emitting electromagnetic<br />

waves which may disturb the control system thus<br />

causing malfunction <strong>of</strong> the unit .<br />

11. Location free from flammable gases , carbon fibre , or<br />

ignitable dust suspensions in the air or where volatile<br />

flames are handled like gasoline or thinner. Operating in<br />

such conditions may result in fire.<br />

Safety Precautions<br />

12. Install the indoor and outdoor units, power sup<strong>pl</strong>y wiring<br />

and connecting wires at least 1m. away from televisions<br />

or radios in order to prevent image interference or noise.<br />

(Depending on the radio waves, a distance <strong>of</strong> 1m. may<br />

not be sufficient enough to eliminate the noise.)<br />

13. Consider whether the <strong>pl</strong>ace where the unit will be<br />

installed can support the full weight <strong>of</strong> the unit, and reinforce<br />

it with boards and beams, etc. if needed before<br />

proceeding with the installation. Also, reinforce the <strong>pl</strong>ace<br />

to prevent vibration and noise before installing. (The<br />

installation pitch can be found on the paper pattern for<br />

installation (3), so refer to it when considering the<br />

necessity for reinforcing the location.)<br />

14. Obey the local and national regulations and limits<br />

regarding airconditioner installation.<br />

15. Location free from lavatory (NH3.etc.). NH3 gas will<br />

cause corrosion <strong>of</strong> outdoor unit metallic parts.<br />

4.1.4 For the following items, take special care during construction and check<br />

after installation is finished<br />

1. Items to be checked after com<strong>pl</strong>etion <strong>of</strong> work<br />

Unit<br />

Are the indoor and outdoor unit fixed firmly? The units may drop, vibrate or make noise.<br />

Is the gas leak test finished? It may result in insufficient cooling.<br />

Is the unit fully insulated? Condensate water may drip.<br />

Does drainage flow smoothly? Condensate water may drip.<br />

Does the power sup<strong>pl</strong>y voltage correspond to that<br />

shown on the name <strong>pl</strong>ate?<br />

The unit may malfunction or the components burn out.<br />

Are wiring and piping correct? The unit may malfunction or the components burn out.<br />

Is the unit safely grounded? It may be dangerous at electric leakage.<br />

Is wiring size according to specifications? The unit may malfunction or the components burn out.<br />

Is something blocking the air outlet or inlet <strong>of</strong><br />

either the indoor or outdoor units?<br />

It may result in insufficient cooling.<br />

Are refrigerant piping length and additional<br />

refrigerant charge noted down?<br />

The refrigerant charge in the system is not clear.<br />

CAUTION<br />

NOTE<br />

Items to be checked If not properly done, what is likely to occur Check<br />

• Be very careful about product transportation.<br />

Some products use PP bands for packaging. Do not use any PP bands for a means <strong>of</strong> transportation. It is dangerous.<br />

• Safely dispose <strong>of</strong> the packing materials.<br />

Packing materials, such as nails and other metal or wooden parts, may cause stabs or other injuries.<br />

Tear apart and throw away <strong>pl</strong>astic packaging bags so that children will not <strong>pl</strong>ay with them. If children <strong>pl</strong>ay with a <strong>pl</strong>astic<br />

bag which was not torn apart, they face the risk <strong>of</strong> suffocation.<br />

• Install the indoor and outdoor units, power sup<strong>pl</strong>y wiring and connecting wires at least 1m. away from televisions<br />

or radios in order to prevent image interference or noise.<br />

(Depending on the radio waves, a distance <strong>of</strong> 1m. may not be sufficient enough to eliminate the noise.)<br />

Installation <strong>of</strong> outdoor unit 357