03.06.2013 Views

1 - page screenshot of chlodzenie.pl

1 - page screenshot of chlodzenie.pl

1 - page screenshot of chlodzenie.pl

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Electric Characteristics 5CSL0-06B<br />

2.2.11 Electric Characteristics<br />

Unit<br />

Power Compressor OFM<br />

Model Type Hz Voltage Voltage range MCA MOP MSC RLA kW FLA<br />

AUUW426D[UU42W U3D]<br />

AUUW486D[UU48W U3D]<br />

AUUW606D[UU60W U3D]<br />

AUUW428D[UU43W U3D]<br />

AUUW488D[UU49W U3D]<br />

AUUW608D[UU61W U3D]<br />

1 Phase<br />

inverter<br />

3 Phase<br />

inverter<br />

50<br />

50<br />

220-240<br />

380-415<br />

Notes :<br />

1. Voltage range<br />

Voltage sup<strong>pl</strong>ied to the unit terminals should be within the<br />

minimum and maximum range<br />

2. Maximum allowable voltage unbalance between phase is 2 %<br />

3. MCA / MOP<br />

MCA = (1.25 x Load1) + Load2 + Load3<br />

MOP = (2.25 x Load1) + Load2 + Load3<br />

- Load1 : Rated running current <strong>of</strong> largest motor<br />

(compressor or other motor)<br />

- Load2 : sum <strong>of</strong> current for all other motors<br />

- Load3 : any other load rated 1.0A or more<br />

4. Select wire spec. based on the MCA<br />

5. Recommended circuit breaker is ELCB (Earth Leakage circuit<br />

breaker)<br />

6. MSC & RLA are measured as the compressor only test<br />

condition.<br />

7. MSC values<br />

Min.: 198<br />

Max.: 264<br />

Min.: 352<br />

Maxi.: 457<br />

22.45 39.45 14.20 17.00 0.24 1.20<br />

26.20 46.20 14.20 20.00 0.24 1.20<br />

31.83 56.33 14.20 24.50 0.24 1.20<br />

6.55 10.83 4.28 4.28 0.24 1.20<br />

7.74 12.97 5.23 5.23 0.24 1.20<br />

8.59 14.50 5.91 5.91 0.24 1.20<br />

8. RLA is measured during each individual compressor test<br />

condition.<br />

9. OFM is measured as the outdoor unit test condition<br />

(Exam<strong>pl</strong>e) Selection <strong>of</strong> proper circuit breaker<br />

① Model : AUUW486D<br />

- Rated running current : 20.0A (refer to spec. sheet)<br />

② MCA = (1.25 x Load1) + Load2 + Load3<br />

= (1.25 x 20.0) + 0 + 1.20 = 26.2A<br />

③ MOP = (2.25 x Load1) + Load2 + Load3<br />

= (2.25 x 20.0) + 0 + 1.20 = 46.2A<br />

→ Finally select circuit breaker 50A<br />

MCA : Minimum Circuit Amperes (A)<br />

MOP : Maximum rating over current protective device<br />

MSC : Maximum Starting Current<br />

RLA : Rated Load Amperes (A)<br />

OFM : Outdoor Fan Motor<br />

kW : Fan Motor rated output (kW)<br />

FLA : Full Load Amperes (A)<br />

240 Outdoor unit - DC Inverter SINGLE A - Synchro (1Ø, 3Ø)

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!