5CSL0-06B Ceiling cassette 4-way<br />

3.2.2 Selection <strong>of</strong> the best location<br />

• There should not be any heat source or steam near the<br />

unit.<br />

• There should not be any obstacles to the air circulation.<br />

• There should be provision <strong>of</strong> easy condensate drain.<br />

• Taking into accounting the noise prevention criteria, spot<br />

the installation location.<br />

• Do not install the unit near the door way.<br />

• Keep proper distances, <strong>of</strong> the unit, from ceiling, fence,<br />

floor, walls and other obstacles as shown in figure.<br />

• The indoor unit must have the maintenance space.<br />

NOTE<br />

Ceiling<br />

False ceiling<br />

1500 or<br />

more<br />

Above figure means minimum value. Please keep these<br />

value at least.<br />

If H is 2700~3200: High ceiling operation control requied<br />

If H is ~2700: Normal operation<br />

1500 or more<br />

1500<br />

or more<br />

20 or more<br />

1500 or more<br />

H<br />

Floor<br />

1500 or<br />

more<br />

1500 or more<br />

False ceiling<br />

1500 or more<br />

Unit:mm<br />

3.2.3 Precautions regarding cassette<br />

indoor unit installation<br />

1) Main points about the indoor installation<br />

• In case <strong>of</strong> high height ceiling<br />

In general commercial <strong>pl</strong>aces and <strong>of</strong>fices though the<br />

height <strong>of</strong> the ceiling is 2.7 m, the ceiling height can be 3<br />

m. In such cases because <strong>of</strong> the temperature difference<br />

with the floor the heating effect can fall down.<br />

High elevation<br />

<strong>of</strong> the ceiling<br />

Discharge<br />

• Countermeasure method<br />

① Air conditioner must be able to operate in high ceiling<br />

conditioner.<br />

② Plan to install the circulator.<br />

③ The air discharge port is made to give more airflow to the<br />

down wood directions.<br />

④ The gate or exit <strong>of</strong> the building is protected by dual door<br />

system.<br />

2) In case the floor or surfaces <strong>of</strong> the <strong>pl</strong>ace<br />

to be air conditioned is in direct contact<br />

with the outdoor air<br />

• The floor <strong>of</strong> the heating room indirect contact with<br />

the storeroom, garage or the outside air receives<br />

the cold air at the floor and the floor temperature<br />

decrease will feel cold at the feet.<br />

Outdoor side<br />

In such <strong>pl</strong>aces where the feet comes in direct contact<br />

with floors will give a cold feeling to the floor.<br />

Installation <strong>of</strong> indoor unit 323<br />

Suction<br />

Hot air<br />

Cold air<br />

Indoor<br />

Outdoor side<br />

Garage<br />

Outdoor<br />

side (Entering <strong>of</strong> air by<br />

frequent opening<br />

and closing <strong>of</strong> door)<br />

Low temperature<br />

<strong>of</strong> the floor<br />

(50~100mm<br />

Insulation required)<br />

Outdoor side