Capacity coefficient factor (Reference) 5CSL0-06B<br />

3) Calculation <strong>of</strong> actual system capacity<br />

① Outdoor unit rated capacity<br />

Qodu(rated) [from specification table]<br />

② Outdoor unit capacity at Ti, To temperature.<br />

Qodu(Ti, To) [from capacity table]<br />

③ Outdoor unit capacity coefficient factor<br />

F(Ti, To) = Qodu(Ti, To) / Qodu(rated)<br />

④ Piping correction factor [from capacity coefficient factor table]<br />

Fmain (length, elevation) for main piping length or elevation<br />

Fbranch (length, elevation) for branch piping length or elevation<br />

⑤ Individual indoor unit combinational capacity<br />

Qidu (combi) = Qodu(rated) x Qidu(rated) / Qidu(rated-total)<br />

⑥ Individual indoor unit actual capacity<br />

Qidu (actual) = Qodu(combi) x F(Ti, To) x Fmain (length, elevation) x Fbranch (length, elevation)<br />

Exam<strong>pl</strong>e) • Outdoor unit model : AUUW486D[UU48W U3D]<br />

• Total indoor units combination : UT24 + UT24<br />

• Outdoor temperature : 32.0°CDB<br />

• Indoor temperature: 19.0°WDB<br />

• Main piping length(O/D to BD):40m<br />

• Branch piping length(BD to I/D):10m<br />

• Indoor unit actual cooling capacity<br />

- Qodu(rated) : 14.0 kW<br />

- Qodu(Ti, To) : 14.4 kW<br />

- F(Ti, To) : 14.4 / 14.0 = 1.03%<br />

- Fmain (length, elevation) = 91.1%<br />

- Fbranch (length, elevation) = 97.8%<br />

- Qidu(actual) [UT24 + UT24] = 14.0 kW x 1.03 x 0.911 x 0.978 = 12.85kW<br />