03.06.2013 Views

1 - page screenshot of chlodzenie.pl

1 - page screenshot of chlodzenie.pl

1 - page screenshot of chlodzenie.pl

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Air tight test 5CSL0-06B<br />

2.6 Air tight test<br />

2.6.1 Air purging<br />

Air and moisture remaining in the refrigerant system have<br />

undesirable effects as indicated below.<br />

① Pressure in the system rises.<br />

② Operating current rises.<br />

③ Cooling (or heating) efficiency drops.<br />

④ Moisture in the refrigerant circuit may freeze and block<br />

capillary tubing.<br />

⑤ Water may lead to corrosion <strong>of</strong> parts in the refrigeration<br />

system. Therefore, the indoor/outdoor unit and connecting<br />

tube must be checked for leak tight, and vacuumed<br />

to remove incondensable gas and moisture in the system.<br />

Checking method<br />

1) Preparation<br />

• Check that each pipe (both liquid and gas side pipes)<br />

between the indoor and outdoor units have been properly<br />

connected and all wiring for the test run has been com<strong>pl</strong>eted.<br />

Remove the service valve caps from both the gas<br />

and the liquid side on the outdoor unit. Check that both the<br />

liquid and the gas side service valves on the outdoor unit<br />

are kept closed at this stage.<br />

2) Leakage test<br />

• Connect the manifold valve (with pressure gauges) and<br />

dry nitrogen gas cylinder to this service port with charge<br />

hoses.<br />

CAUTION<br />

Be sure to use a manifold valve for leakage test. If it is<br />

not available, use a stop valve for this purpose. The "Hi"<br />

knob <strong>of</strong> the manifold valve must always be kept close.<br />

Outdoor unit<br />

Gas Pipe pipe Pipe<br />

Liquid Pipe<br />

pipe<br />

Manifold gauge hose<br />

Manifold valve<br />

Pressure<br />

gauge<br />

Charge hose<br />

Nitrogen gas<br />

cylinder(in vertical<br />

standing position)<br />

Lo Hi<br />

CAUTION<br />

To avoid nitrogen entering the refrigerant system<br />

in a liquid state, the top <strong>of</strong> the cylinder must be higher<br />

than its bottom when you pressurize the system. Usually,<br />

the cylinder is used in a vertical standing position.<br />

1. Do a leakage test <strong>of</strong> all joints <strong>of</strong> the Tubing (both<br />

indoor and outdoor) and both gas and liquid side service<br />

valves. Bubbles indicate a leak. Be sure to wipe<br />

<strong>of</strong>f the soap with a clean cloth.<br />

2. After the system is found to be free <strong>of</strong> leaks, relieve the<br />

nitrogen pressure by loosening the charge hose connector<br />

at the nitrogen cylinder. When the system pressure<br />

is reduced to normal, disconnect the hose from<br />

the cylinder.<br />

2.6.2 Essential points <strong>of</strong> testing<br />

The key to successful testing is strict adherence to<br />

the following procedure:<br />

a) The liquid and gas piping in each refrigerant system<br />

should be pressurized in turn in accordance with the<br />

following steps. (Nitrogen gas must be Manifold used.) gauge<br />

Step 1: increase pressure to 0.3MPa<br />

for 3 minutes or more<br />

Step 1: increase pressure to 1.5MPa<br />

for 3 minutes or more<br />

Step 3: increase pressure to 3.8MPa<br />

for approxmate 24 hours<br />

Liquid Pipe<br />

Indicates existence<br />

<strong>of</strong> major leaks<br />

Indicates existence<br />

<strong>of</strong> major leaks<br />

310 Guideline for each installation process<br />

Gas Pipe<br />

Increasing the system pressure to 3.8MPa does not guarantee<br />

the identification <strong>of</strong> minor leaks if pressure is maintained<br />

for only a short time. It is therefore recommended<br />

that the system remain pressurized in accordance with<br />

Step 3 above for at least 24 hours.<br />

NOTE<br />

Piping should not be pressured more than 3.8MPa.<br />

b) Check for pressure drop<br />

If there is no drop in pressure then the test is deemed a<br />

success.<br />

If the pressure drops then the leak must be located. See<br />

following <strong>page</strong>.<br />

However, if there is a change in the ambient temperature<br />

between the pressurizing stage and the time when<br />

you check for a drop in pressure then you will have to<br />

adjust your calculations accordingly since a change <strong>of</strong><br />

1°C can account for a pressure change <strong>of</strong> approximately<br />

0.01MPa.<br />

Compensating adjustment value:<br />

(temperature at time <strong>of</strong> pressurizing – temperature at<br />

time <strong>of</strong> checking) × 0.01

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!