8 DETERMINING SITE-SPECIFIC LOADS Volume II<br />

EXAMPLE 8.5. ROOF UPLIFT CONNECTOR LOADS<br />

Given:<br />

• Roof span of 24 ft with 2-ft overhangs<br />

• Roof/ceiling dead load of 10 psf<br />

• Wind load based on 150 mph, Exposure C at 33-ft mean roof height<br />

• Building is enclosed<br />

• K z = 1.0 (velocity pressure exposure coefficient evaluated at height of 33 ft)<br />

• K zt = 1.0 (topographic factor)<br />

• K d = 0.85 (wind directionality)<br />

Illustration A. Roof-to-wall uplift connection loads from wind forces<br />

Find: The roof-to-wall uplift connection load using the envelope procedure for low-rise buildings (see<br />

Figure 28.4-1 in ASCE 7-10).<br />

Solution: The roof-to-wall uplift connection load can be found using the envelope procedure for lowrise<br />

buildings as follows:<br />

• The velocity pressure (q) for the site conditions is determined from Equation 8.13 as follows:<br />

8-54 COASTAL CONSTRUCTION MANUAL