8 DETERMINING SITE-SPECIFIC LOADS Volume II<br />

EXAMPLE 8.8. LATERAL CONNECTION FRAMING LOADS FROM WIND<br />

Given:<br />

• Wind load is based on 150 mph, Exposure C at 33-ft mean roof height, and wall and<br />

diaphragm framing as shown in Illustration A<br />

• Building is enclosed<br />

• Wall height is 10 ft<br />

• Stud spacing is 16 in. o.c.<br />

• Sheathing effective area is 10 ft 2<br />

• ASD velocity pressure q = 29.38 psf (from Example 8.5)<br />

• Wall suction equations for Zone 4 and Zone 5 are provided in Example 8.7<br />

• Internal pressure coefficient for wall sheathing is GC pi = +/- 0.18<br />

Illustration A. Lateral connector loads for wall-to-roof and wall-to-floor connections<br />

Find: Framing connection requirements at the top and base of the wall.<br />

Solution: The connector load can be determined as follows:<br />

8-66 COASTAL CONSTRUCTION MANUAL