Volume II DESIGNING THE BUILDING 9<br />

8. The requirement for separation of the foundation elements between townhouse units makes structural<br />

rigidity in the direction parallel to the shore more difficult to achieve. If the houses in Figure 9-32 were<br />

in a seismic hazard area, the designer could decide to place diagonal bracing parallel to the shore (i.e.,<br />

perpendicular to the primary flood flow direction) or use more closely spaced and larger piles. Diagonal<br />

bracing would provide rigidity but would also create an obstruction below the DFE. The design<br />

professional should consult <strong>FEMA</strong> NFIP Technical Bulletin 5 (<strong>FEMA</strong> 2008c) for information about<br />

the types of construction that constitute an obstruction.<br />

One solution to some of the issues illustrated by Figure 9-32 would be to use two parallel independent walls<br />

to provide the required fire separation between units. Each wall could be attached to the framing system<br />

of the unit on one side of the separation and supported by a beam running perpendicular to the shore and<br />

bearing on the open foundation of that unit.<br />

9.4.5 Corrosion<br />

Modern construction techniques often rely heavily on metal<br />

fasteners and connectors to resist the forces of various coastal<br />

hazards. To be successful, these products must have lifetimes<br />

that are comparable to those of the other materials used for<br />

construction. Near saltwater coastlines, corrosion has been<br />

found to drastically shorten the lifetime of standard fasteners<br />

and connectors. Corrosion is one of the most underestimated<br />

COASTAL CONSTRUCTION MANUAL<br />

Figure 9-32.<br />

Townhouse framing<br />

system<br />

CROSS REFERENCE<br />

For additional information about<br />

corrosion of metal connectors in<br />

coastal construction, see <strong>FEMA</strong><br />

NFIP Technical Bulletin 8-96.<br />

hazards affecting the overall strength and lifetime of coastal buildings. To be successful, hazard-resistant<br />

buildings must match the corrosion exposure of each element with the proper corrosion-resistant material.<br />

9-37