11 Designing the builDing envelope Volume II<br />

Figure 11-34.<br />

A bleeder strip (doublearrow)<br />

that was used at<br />

a rake blow-off; lack of<br />

contact between the tab<br />

of the overlying shingle<br />

and the bleeder’s self-seal<br />

adhesive (upper arrow).<br />

Estimated wind speed: 125<br />

mph. Hurricane Katrina<br />

(Mississippi, 2005)<br />

Figure 11-35.<br />

Inadequate sealing of the<br />

self-sealing adhesive at<br />

a hip as a result of the<br />

typical hip installation<br />

procedure. Estimated<br />

wind speed: 105 mph.<br />

Hurricane Katrina<br />

(Mississippi, 2005)<br />

Four fasteners per shingle are normally used where the basic wind speed is less than 115 mph.16 Where<br />

the basic wind speed is greater than 115 mph, six fasteners per shingle are recommended. Fact Sheet 7.3 in<br />

<strong>FEMA</strong> P-499 provides additional guidance on shingle fasteners. Storm damage investigations have shown<br />

that signifcant fastener mislocation is common on damaged roofs. When nails are too high above the<br />

nail line, they can miss the underlying shingle headlap or have inadequate edge distance, as illustrated<br />

16 The 115-mph basic wind speed is based on ASCE 7-10, Risk Category II buildings. If ASCE 7-05 or an earlier version is used, the<br />

equivalent wind speed trigger is 90 mph.<br />