Volume II DETERMINING SITE-SPECIFIC LOADS 8<br />

EXAMPLE 8.6. LATERAL DIAPHRAGM LOADS FROM WIND PERPENDICULAR TO<br />

RIDGE (continued)<br />

• w = wall<br />

Wall interior zone<br />

the same direction)<br />

Wall end zone<br />

in the same direction)<br />

COASTAL CONSTRUCTION MANUAL<br />

(note that leeward and windward forces are acting in<br />

(note that leeward and windward forces are acting<br />

Under the procedures and notes shown in Figure 28.4-1 of ASCE 7-10, end zones extend a<br />

minimum of 3 ft at each end of the wall. For long or tall walls, end zone lengths are based on<br />

10 percent of the least horizontal dimension or 40 percent of the mean roof height, whichever is<br />

smaller, but not less than either 4 percent of the least horizontal dimension or 3 ft at each end of<br />

the wall. The end zone width where the pressures are applied is 3 ft.<br />

The average pressure on the wall is:<br />

where:<br />

24 ft = building length assumed to be equal to the roof span for purposes of accounting for<br />

average effects of pressure differences at end zones and interior zones<br />

Roof interior zone<br />

the same direction)<br />

Roof end zone<br />

(note that leeward and windward forces are acting in<br />

8-59