Volume II DETERMINING SITE-SPECIFIC LOADS 8<br />

EXAMPLE 8.8. LATERAL CONNECTION FRAMING LOADS FROM WIND (concluded)<br />

• C&C coefficients are used<br />

• When determining C&C pressure coefficients, the effective wind area equals the tributary area<br />

of the framing members<br />

• For long and narrow tributary areas, the area width may be increased to one-third the framing<br />

member span to account for actual load distributions<br />

• The larger area results in lower average wind pressures<br />

• The increase in width for long and narrow tributary areas applies only to calculation of wind<br />

pressure coefficients<br />

• Determine the tributary area and pressure coefficient GC pf for the wall sheathing: Stud<br />

effective wind area equals 13.33 ft 2 . The minimum required area for analysis is h 2 /3=33.3 ft 2 ,<br />

where h is 10 ft<br />

• In accordance with ASCE 7-10, the pressure coefficient, GC pf , for wall sheathing can be<br />

determined based on a minimum effective wind area of 33.3 ft 2 as follows:<br />

Zone 5:<br />

The design wind pressure is determined as follows from Equation 8.14:<br />

Zone 5:<br />

The required capacity of connectors assuming load is based on half the wall height:<br />

Zone 5:<br />

Note: This solution matches the information in Table 8-9.<br />

8.8 Tornado Loads<br />

Tornadoes have wind speeds that vary based on the magnitude<br />

of the event; more severe tornadoes have wind speeds that are<br />

significantly greater than the minimum design wind speeds<br />

required by the building code. Designing an entire building<br />

to resist tornado-force winds of EF3 or greater based on the<br />

Enhanced Fujita tornado damage scale (in EF2 tornadoes,<br />

large trees are snapped or uprooted) may be beyond the realm<br />

COASTAL CONSTRUCTION MANUAL<br />

WARNING<br />

Safe rooms should be located<br />

outside known flood-prone areas,<br />

including the 500-year floodplain,<br />

and away from any potential large<br />

debris sources. See Figure 5-2<br />

of <strong>FEMA</strong> 320 for more direction<br />

regarding recommended siting<br />

for a safe room.<br />