13 CONSTRUCTING THE BUILDING Volume II<br />

Figure 13-22.<br />

Full-height sheathing to<br />

improve transfer of shear<br />

The design drawings may show tiedown connections between large shearwall vertical posts and main girders.<br />

Especially in larger, taller buildings, these connections must resist thousands of pounds of overturning<br />

forces during high winds. See Section 8.7 for information regarding the magnitude of these forces. The<br />

connections must be accomplished with careful layout, boring, and assembly. Shear transfer nailing at the<br />

top plates and sills must be in accordance with the design. Proper nailing and attachment of the framing<br />

material around openings is very important; see Section 9.2.1 for a discussion of the difficulty of transferring<br />

large shear loads when there are large openings in the shearwall.<br />

It is very important that shearwall sheathing (e.g., plywood, oriented strand board [OSB]) with an<br />

exterior exposure be finished appropriately with pigmented finishes such as paint, which last longer than<br />

unpigmented finishes, or semitransparent penetrating stains. It is also important that these finishes be<br />

properly maintained. Salt crystal buildup in surface checks in siding can damage the siding. Damage is<br />

typically worse in siding that is sheltered from precipitation because the salt crystals are never washed off<br />

with fresh rainwater.<br />

To meet the design intent, walls must:<br />

Be plumb and square to each other and to the floor<br />

Be lined up over solid support such as a beam, floor joists, or a perimeter band joist<br />

Not have any more openings than designated by the plans<br />

Not have openings located in places other than designated on the plans<br />

Consist of material expected to resist corrosion and deterioration<br />

Be properly attached to the floors above and below the wall, including the holddown brackets required<br />

to transfer overturning forces<br />

13-26 COASTAL CONSTRUCTION MANUAL