20.07.2013 Views

FEMA P55 Coastal Construction Manual, Fourth Edition - Mad Cad

FEMA P55 Coastal Construction Manual, Fourth Edition - Mad Cad

FEMA P55 Coastal Construction Manual, Fourth Edition - Mad Cad

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

8 DETERMINING SITE-SPECIFIC LOADS Volume II<br />

S = snow load<br />

R = rain load<br />

T = self-straining force<br />

W = wind load<br />

Loads combined using the ASD method are considered to act in the following combinations for buildings<br />

in Zone V and <strong>Coastal</strong> A Zone (Section 2.4.1 of ASCE 7-10), whichever produces the most unfavorable<br />

effect on the building or building element:<br />

Combination No. 1: D<br />

Combination No. 2: D + L<br />

Combination No. 3: D + (Lr or S or R)<br />

Combination No. 4: D + 0.75L + 0.75(Lr or S or R)<br />

Combination No. 5: D + (0.6W or 0.7E)<br />

Combination No. 6a: D + 0.75L + 0.75(0.6W) + 0.75(Lr or S or R)<br />

Combination No. 6b: D + 0.75L + 0.75(0.7E) + 0.75S<br />

Combination No. 7: 0.6D + 0.6W<br />

Combination No. 8: 0.6D + 0.7E<br />

When a structure is located in a flood zone, the following load combinations should be considered in<br />

addition to the basic combinations in Section 2.4.1 of ASCE 7-10:<br />

In Zone V or <strong>Coastal</strong> A Zone, 1.5F a should be added to load combinations Nos. 5, 6, and 7, and<br />

E should be set equal to zero in Nos. 5 and 6<br />

In the portion of Zone A landward of the LiMWA, 0.75F a should be added to combinations Nos. 5, 6,<br />

and 7, and E should be set equal to zero in Nos. 5 and 6.<br />

The ASCE 7-10 Commentary states “Wind and earthquake loads need not be assumed to act simultaneously.<br />

However, the most unfavorable effects of each should be considered in design, where appropriate.”<br />

The designer is cautioned that F is intended for fluid loads in tanks, not hydrostatic loads. F a should be<br />

used for all flood loads, including hydrostatic loads, and should include the various components of flood<br />

loads as recommended in Section 8.5.11 in this chapter. It is important to note that wind and seismic loads<br />

acting on a building produce effects in both the vertical and horizontal directions. The load combinations<br />

discussed in this section must be evaluated carefully, with consideration given to whether a component of<br />

the wind or seismic load acts in the same vertical or horizontal direction as other loads in the combination.<br />

In some cases, gravity loads (dead and live loads) may counteract the effect of the wind or seismic load,<br />

either vertically or horizontally. Building elements submerged in water have a reduced effective weight due<br />

to buoyancy. Example 8.10 illustrates the use of load combinations for determining design loads.<br />

8-74 COASTAL CONSTRUCTION MANUAL

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!