Table 3 Sensitivity of Statistical FDD method (low-cost design) on a rooftop unit with a<br />

fixed orifice.<br />

Per<strong>for</strong>mance Refrigerant Liquid Line Compressor Condenser Evaporator<br />

Index<br />

Leakage Restriction Valve Leak Fouling Fouling<br />

(% Leakage) (% ∆P) (% ∆η v ) (% Lost area) (% Lost flow)<br />

1st All 1st All 1st All 1st All 1st All<br />

<strong>Fault</strong> Level (%) 9.7 12.5 9.0 10.5 17.5 20.0 16.4 19.5 27.2 Max<br />

% Loss Capacity 5.5 7.1 4.6 5.4 10.7 12.2 3.2 3.6 15.3 >19.4<br />

% Loss COP 3.2 4.1 3.3 3.8 11.9 13.6 4.6 6.2 13.5 >17.4<br />

∆Τ sh 9.2 10.5 7.8 8.9 -5.9 -6.8 -1.9 -3.0 -4.6 4.6 1.3 2.5 3.9 7.9 3.4 5.1 4.9 10.3<br />

∆Τ sh 5.4 > 11 2.3 4.8 -1.8 -3.6 -0.6 -1.6 -1.7 -2.7<br />

∆T hg 4.8 > 10 2.4 4.8 0.0 0.0 1.8 2.3 -1.2 -2.7<br />