Fault Detection and Diagnostics for Rooftop Air Conditioners

Fault Detection and Diagnostics for Rooftop Air Conditioners

Fault Detection and Diagnostics for Rooftop Air Conditioners

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

67<br />

normal _ value − current _ value<br />

normal _ value<br />

The normal value is predicted using an overall system per<strong>for</strong>mance model which<br />

is built based on system manufacturer rating data. The model inputs are condenser inlet<br />

air dry-bulb temperature <strong>and</strong> evaporator wet-bulb temperature.<br />

The compressor overheat degradation is defined by,<br />

current _ Tdis<br />

− normal _ T<br />

max_ ∆T<br />

dis<br />

dis<br />

The maximum<br />

∆ Tdis<br />

is found to be around 40 F by Chen’s data (2000), which<br />

should be confirmed by more investigation. There is difficulty to predict normal values<br />

<strong>for</strong> T<br />

dis<br />

because there is no overall system state model available. For this demonstration,<br />

it is assumed that the system driving condition is not changed much <strong>and</strong> the measured<br />

value at the fault free condition is used as the normal value. Further research should be<br />

done later to find an inexpensive safety indicator <strong>for</strong> a compressor.<br />

4.2.2.4 FDD Report Window (FDDRW)<br />

To help customers make a decision whether to service the diagnosed fault or not,<br />

the FDD Report Window generates a tabular report <strong>for</strong> the FDD results including<br />

diagnosed faults <strong>and</strong> relative severity indicators <strong>and</strong> system per<strong>for</strong>mance <strong>and</strong> safety<br />

degradation indices, <strong>and</strong> provides an FDD recommendation. In this demo, the FDD<br />

recommendation is based on per<strong>for</strong>mance <strong>and</strong> safety degradation. If the per<strong>for</strong>mance<br />

degradation is over twenty per cent or the compressor is overheated up to ninety per cent,<br />

service is recommended. More investigation is needed <strong>for</strong> fault recommendation.

Hooray! Your file is uploaded and ready to be published.