15<br />

Figure E-4 Histogram of the EER degradation<br />

Tables E-1, E-2, E-3, <strong>and</strong> E-4 summarize FDD results <strong>for</strong> the other field sites.<br />

Eleven of the twenty-one investigated RTUs have liquid-line restriction faults, ten of<br />

them have refrigerant charge faults, <strong>and</strong> eight of them have more than two simultaneous<br />

faults. Service would be justified <strong>for</strong> nine of the twenty-one investigated RTUs.<br />

<strong>Fault</strong>s<br />

Refrigerant<br />

Charge<br />

Liquid-line<br />

Restriction<br />

Evaporator<br />

Fouling<br />

Recommended<br />

Service<br />

Table E-1 FDD results <strong>for</strong> modular school site<br />

Woodl<strong>and</strong><br />

Oakl<strong>and</strong><br />

RTU1 RTU2 RTU1 RTU2<br />

Normal Normal Normal Over Charge<br />

Restriction<br />

Severe<br />

Restriction<br />

Restriction<br />

Normal<br />

Normal Normal Normal Fouling<br />

Not yet<br />

Arrange<br />

Service<br />

Not yet<br />

Arrange Service