64<br />

bypass the compressor. At this time, four faults existed simultaneously in the<br />

system: refrigerant low charge, condenser fouling, liquid line restriction, <strong>and</strong><br />

compressor leakage.<br />

The following steps describe the removal of faults,<br />

5. After the system ran <strong>for</strong> half an hour under four faults, the paper covering the<br />

condenser was removed. There existed three simultaneous faults in the system:<br />

refrigerant low charge, liquid line restriction, <strong>and</strong> compressor leakage, which is<br />

a different combination than step three.<br />

6. Half an hour later, the liquid line restriction fault was removed by fully opening<br />

the liquid line restriction valve. At this time, refrigerant low charge <strong>and</strong><br />

compressor leakage existed in the system, which is a different combination than<br />

step two.<br />

7. Half an hour later, the compressor bypass valve was closed to remove<br />

compressor leakage fault. There was only refrigerant low charge fault in the<br />

system.<br />

8. Finally, half an hour later, the system was charged up to a nominal refrigerant<br />

level. The system was supposed to run normally.<br />

2.2.2 <strong>Fault</strong> <strong>Detection</strong> <strong>and</strong> Diagnosis Window<br />

This window plots the normalized fault indicator <strong>for</strong> four individual faults using<br />

color bars: refrigerant low charge (Low-Charge), condenser fouling (Cond-Foul), liquid<br />

line restriction (LL-Restr), <strong>and</strong> compressor leakage (Comp-Leak).<br />

The normalized fault indicator is the ratio of the current feature value to the<br />

predefined value, which is defined at an individual fault level causing 20% cooling<br />

capacity degradation.<br />

Normalized<br />

_ <strong>Fault</strong> _ Indicator =<br />

current _ feature − value<br />

predefined _ feature _ value<br />

64