79<br />

Figure 4-26 Histogram bar plot of the normalized fault indicator <strong>for</strong> compressor valve<br />

leakage<br />

In summary, the system has three faults, low refrigerant charge, liquid line<br />

restriction <strong>and</strong> condenser fouling. To assess the impact of the diagnosed faults on the<br />

overall system per<strong>for</strong>mance, Figure 4-27 plots the cooling capacity degradation. It can be<br />

seen that the system cooling capacity was degraded 23~45% <strong>and</strong> the average is about<br />

32%, which is coincident with the value indicated by refrigerant charge fault indicator.<br />

The cooling capacity degradation can be confirmed by investigating the return air<br />

temperature <strong>and</strong> system running time. It can be seen from Figure 4-28 that the average<br />

return air temperature is around 78 F <strong>and</strong> the highest is 88 F, which does not satisfy the<br />

com<strong>for</strong>t criteria. From Figure 4-29, it can be seen that the system kept running<br />

continuously <strong>for</strong> a long time (average is 2.5 hours <strong>and</strong> maximum is up to 9 hours) in<br />

order to remove the heat load. So, from the com<strong>for</strong>t criteria, service should be done to<br />

correct the diagnosed faults in order to maintain com<strong>for</strong>t.