66<br />

<strong>for</strong> T<br />

dis<br />

because there is no overall system state model available. For this demonstration,<br />

it is assumed that the system driving condition is not changed much <strong>and</strong> the measured<br />

value at the fault free condition is used as the normal value. Further research should be<br />

done later to find an inexpensive safety indicator <strong>for</strong> a compressor.<br />

2.2.4 FDD Report Window<br />

To help customers make a decision whether to service the diagnosed fault or not,<br />

the FDD Report Window generates a tabular report <strong>for</strong> the FDD results including<br />

diagnosed faults <strong>and</strong> relative severity indicators <strong>and</strong> system per<strong>for</strong>mance <strong>and</strong> safety<br />

degradation indices, <strong>and</strong> provides an FDD recommendation. In this demo, the FDD<br />

recommendation is based on per<strong>for</strong>mance <strong>and</strong> safety degradation. If the per<strong>for</strong>mance<br />

degradation is over twenty per cent or the compressor is overheated up to ninety per cent,<br />

service is recommended. More investigation is needed <strong>for</strong> fault recommendation.<br />

2.2.5 Output of the FDD Demonstration<br />

This section provides sample outputs of the FDD demonstration after each fault<br />

was added <strong>and</strong> removed (watch the movie <strong>for</strong> details).<br />

Figure 2-13 captures a movie frame when the system was running at low<br />

refrigerant charge (step 1 of section 2.2.1). The “<strong>Fault</strong> <strong>Detection</strong> <strong>and</strong> Diagnosis window<br />

(FDDW)” indicates that there existed a refrigerant low charge fault whose fault severity<br />

was around 0.45. The “System Per<strong>for</strong>mance & Safety Degradation Window (SPSDW)”<br />

plots the overall degradations, all of which were less than 20%. The “FDD Report<br />

Window (FDDRW)” summarizes the indicates <strong>and</strong> generates the FDD report table <strong>and</strong><br />

recommended that “although there is (are) fault(s) with minor impacts on overall system<br />

per<strong>for</strong>mance, it may be not worthwhile to service so far”.<br />

66