Fault Detection and Diagnostics for Rooftop Air Conditioners

Fault Detection and Diagnostics for Rooftop Air Conditioners

Fault Detection and Diagnostics for Rooftop Air Conditioners

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

38<br />

charge faults <strong>for</strong> TXV RTU systems. Three Trane RTUs (a 2.5-ton split system, a 5-ton<br />

packaged system <strong>and</strong> a 7.5-Ton split system) were tested under four operation conditions<br />

(see Table 2-3) with various charge levels.<br />

Table 2-3 Environmental conditions.<br />

Test<br />

Condition<br />

T outdoor ,<br />

°C<br />

T indoor ,<br />

°C<br />

T dew point ,<br />

°C<br />

A 35.00 26.67 15.77<br />

B 27.78 26.67 15.77<br />

C 27.78 26.67 < 3.06<br />

HT 48.89 26.67 15.77<br />

2.3 Field Test Facilities<br />

All the field-sites in Cali<strong>for</strong>nia are small commercial buildings that utilize<br />

packaged air conditioning <strong>and</strong> heating equipment. The criteria used <strong>for</strong> selecting the<br />

field-sites included: 1) building occupancy type <strong>and</strong> size; 2) HVAC system installed, <strong>and</strong><br />

3) climate region. The types of building include smaller retail stores, restaurants <strong>and</strong><br />

modular schoolrooms. The HVAC systems installed include different rooftop <strong>and</strong> wall<br />

mounted units with different capacities <strong>and</strong> manufactured by York, Trane <strong>and</strong> Bard. The<br />

climates include two different macroclimate types: coastal <strong>and</strong> inl<strong>and</strong>. Table 2-4<br />

summarizes in<strong>for</strong>mation about all sites (refer to Deliverables 2.1.1a & 2.1.1b <strong>for</strong> details).<br />

The Purdue field setup is meant to mimic field setups in Cali<strong>for</strong>nia in order to aid<br />

in the identification of installation <strong>and</strong> operational problems locally. In addition, this<br />

setup allows us to test alternative sensors <strong>and</strong> to artificially introduce faults, both of<br />

which would be logistically difficult to per<strong>for</strong>m in Cali<strong>for</strong>nia (refer to Deliverables 2.1.1a<br />

& 2.1.1b).