72<br />

recommended that: the system requires more refrigerant <strong>and</strong> the compressor requires<br />

service.<br />

Figure 2-18 Outputs of the FDD demonstration after removal of liquid line restriction<br />

fault<br />

Figure 2-19 shows one frame after the compressor leakage fault was removed by<br />

closing the discharge line bypass valve (step 7 of section 2.2.1), which was restored to<br />

step 1 of section 2.2.1. FDDW indicates that there existed one fault, refrigerant low<br />

charge with the fault severity over 0.45. Since the overall per<strong>for</strong>mance degradation was<br />

less than 20% at this moment (see SPSDW <strong>and</strong> FDDRW), no service is recommended.<br />

72