33<br />

point sensor placement is generally used, many measurements often are biased <strong>and</strong><br />

noisy. The FDD should be able to h<strong>and</strong>le these practical difficulties.<br />

3. Multiple-simultaneous faults are common <strong>for</strong> packaged air conditioners, so the<br />

FDD technique should be capable of h<strong>and</strong>ling them.<br />

1.3.2 Methodology<br />

There are two aspects to the general approach proposed <strong>for</strong> achieving the<br />

objectives: 1) actively create favorable conditions <strong>for</strong> application of the FDD techniques<br />

<strong>and</strong> 2) provide improved FDD methodologies to h<strong>and</strong>le multiple-simultaneous faults <strong>and</strong><br />

reduced model training requirements.<br />

Because of economic constraints, some practical difficulties are impossible to<br />

overcome passively. For example, it is not possible <strong>for</strong> a single-point sensor to measure<br />

the mixing box temperature accurately under varying damper position. To reduce<br />

measurement uncertainty <strong>and</strong> bias <strong>and</strong> dimensionality, favorable conditions <strong>for</strong> FDD can<br />

be created proactively as follows:<br />

1. Schedule application of the FDD methods at special times (e.g. night time) instead<br />

of around the clock to eliminate the unfavorable impact of weather conditions, such<br />

as solar radiation, <strong>and</strong> occupant intervention.<br />

2. Override routine controls to fix the speed of the condenser fan <strong>and</strong> evaporator<br />

blower <strong>and</strong> damper position. Constant condenser fan <strong>and</strong> evaporator blower speed<br />

is equivalent to constant air mass flow rate under normal operation condition. Fixed<br />

damper position eliminates the mixing problem with single-point sensor.<br />

From a methodology point of view,<br />

1. Existing FDD methods were examined to identify their advantages <strong>and</strong> drawbacks.<br />

The statistical rule-based (SRB) FDD method proposed by Rossi & Braun only<br />

uses low cost sensor <strong>and</strong> has good per<strong>for</strong>mance under laboratory test, so it<br />

provided a start <strong>for</strong> further improvement.<br />

2. The FDD problem was analyzed from a control <strong>and</strong> mathematical point of view.<br />

From the control point of view, decoupling is an efficient way to h<strong>and</strong>le