65<br />

Although the predefined fault level is arbitrary, the author believes that a fault<br />

causing 20% cooling capacity degradation is worthwhile to service.<br />

The normalized fault indicator indicates the relative severity of the individual faults.<br />

However, the refrigerant low charge is a system-level fault <strong>and</strong> its impact on overall<br />

system per<strong>for</strong>mance is not only determined by its own charge level but also other faults,<br />

so the indicator oscillates a lot. Fortunately, data collected so far shows that this<br />

oscillation does not change the decision of the fault detection <strong>and</strong> diagnosis method.<br />

The normalized fault indicators are plotted using color bars. When an indicator is<br />

larger than the threshold, 0.2, it is plotted in red, otherwise in green. According to<br />

experience, an indicated fault level with a per<strong>for</strong>mance degradation less than<br />

0.2*20%=4% is not reliable.<br />

2.2.3 System Per<strong>for</strong>mance & Safety Degradation Window<br />

Capacity <strong>and</strong> COP are usually used as criteria to indicate system per<strong>for</strong>mance.<br />

The compressor is the most expensive part of the system <strong>and</strong> too much overheating<br />

would result in safety problems such as bad lubrication <strong>and</strong> motor short-circuit. So<br />

degradations of these three indices are plotted in this window. The capacity <strong>and</strong> COP<br />

degradations are defined by,<br />

normal _ value − current _ value<br />

normal _ value<br />

The normal value is predicted using an overall system per<strong>for</strong>mance model which<br />

is built based on system manufacturer rating data. The model inputs are condenser inlet<br />

air dry-bulb temperature <strong>and</strong> evaporator wet-bulb temperature.<br />

The compressor overheat degradation is defined by,<br />

The maximum<br />

current _ T<br />

dis<br />

− normal _ T<br />

max_ ∆T<br />

dis<br />

∆ Tdis<br />

is found to be around 40 F by Chen’s data (2000), which<br />

should be confirmed by more investigation. There is difficulty to predict normal values<br />

dis<br />

65