<strong>Precipitator</strong> Alarm Settings<br />
Click on the <strong>Precipitator</strong> Alarm Settings tab to view and edit precipitator alarms. These alarms<br />
are for the entire precipitator in which they are configured. You will need to set these in each<br />
configured system on the precipitator.<br />
<strong>Precipitator</strong> Alarms Tab<br />
Press the Edit button to make changes to the alarm settings.<br />
Use the drop down lists to set the priority of the alarms. The priority can be one of the following:<br />
• Disabled: The alarm condition is disabled. There will be no alarm.<br />
• Event: The condition will cause a low priority event entry in the alarm log.<br />
• Pop-Up: The condition will cause a pop-up window to appear and a low priority alarm.<br />
• Medium: The condition will cause a medium priority alarm entry in the alarm log.<br />
• High: The condition will cause a high priority alarm entry in the alarm log.<br />
Enter a value in the Opacity Above X % to set an alarm condition when opacity rises above the<br />
entered value.<br />
To alarm a specific change in opacity over a set time then enter values in the Opacity increases<br />
X % in Y Hours fields.<br />
To alarm on a specific boiler load then set the drop down list to select Greater/Less Than and<br />
enter a load value in Megawatts.<br />