<strong>Precipitator</strong> <strong>Optimization</strong> <strong>System</strong> 7<br />
<strong>User</strong> <strong>Manual</strong><br />
<strong>Precipitator</strong> Power Interaction<br />
The options in this section determine how MicroRap <strong>Optimization</strong> will operate in situations<br />
where precipitator power is not stable. These situations can be a result of running the Power<br />
<strong>Optimization</strong> module or any of the following events: MVC Off, MVC Tripped, or MVC<br />
Communication Error. Use the radio buttons in each section to select what action MicroRap<br />
<strong>Optimization</strong> will take when these situations occur in each situation.<br />
Select Continue MicroRap <strong>Optimization</strong> using <strong>Precipitator</strong> Power Parameters to have<br />
optimization function as if there was no change.<br />
Select Continue running MicroRap <strong>Optimization</strong> ignoring <strong>Precipitator</strong> Power Conditions to<br />
have optimization continue running but ignoring all conditions using <strong>Precipitator</strong> Power<br />
Parameters.<br />
Select Suspend MicroRap <strong>Optimization</strong> to have optimization temporarily suspend during the<br />
situation. When the situation is resolved optimization will resume running as normal.<br />
Alarm Configuration<br />
MicroRap <strong>Optimization</strong> triggers an alarm when it is turned on or off and when a condition<br />
becomes true causing a program change. The user can set the alarm priority or choose to<br />
disable the alarms by clicking on the appropriate radio button.<br />
Select Disabled to disable alarms. MicroRap <strong>Optimization</strong> will not send any messages to the<br />
alarm log if alarms are disabled.<br />
Select Event to have any optimization change cause an event to be logged in the alarm log.<br />
Select Pop Up to have any optimization change cause POS to create a low priority alarm and a<br />
pop up window for the alarm message.<br />
Select Medium to have any optimization change cause POS to create a medium priority alarm for<br />
the alarm message.<br />
Select High to have any optimization change cause POS to create a high priority alarm for the<br />
alarm message as well as an audible indicator.<br />
Copyright © 2007 <strong>Neundorfer</strong>, <strong>Inc</strong>orporated<br />
Specifications and Features subject to change without notice<br />
08/01/07<br />
52