<strong>Precipitator</strong> <strong>Optimization</strong> <strong>System</strong> 7<br />
<strong>User</strong> <strong>Manual</strong><br />
This section of the screen lists<br />
the number of steps (in order of<br />
execution), the step back<br />
percentage, and the number of<br />
voltage controls in the step.<br />
The Insert Step button will<br />
insert a step at the selected<br />
location.<br />
The Add button will insert a<br />
new step at the end of the<br />
program.<br />
The Delete Step will delete the<br />
selected step.<br />
The step back percentage can<br />
be adjusted by selecting a step<br />
and then adjusting the Percent<br />
bar. The percent bar can be<br />
adjusted by clicking and<br />
dragging the bar, pressing the<br />
up and down arrows or typing a<br />
number in the numerical<br />
readout below the graph. The<br />
Percentage Bar represents a<br />
percentage of full secondary<br />
current for the TR Set.<br />
This is where T/R sets can be added or<br />
removed from the step currently<br />
highlighted in the Step Selection box.<br />
The Available list shows all TR sets for<br />
this precipitator that can be included on<br />
this step of the program. The <strong>Inc</strong>luded<br />
box displays the unit names for the<br />
selected T/R sets in this particular<br />
optimization step.<br />
In the T/R Set Selection box you can<br />
add or delete voltage controls used in<br />
this optimization step. There are two<br />
methods of adding controls. The first<br />
method is visually from the Plan View<br />
window. The other is by selecting T/R<br />
sets from the Available box.<br />
T/R Set Selection Box<br />
Copyright © 2007 <strong>Neundorfer</strong>, <strong>Inc</strong>orporated<br />