<strong>Precipitator</strong> <strong>Optimization</strong> <strong>System</strong> 7<br />

<strong>User</strong> <strong>Manual</strong><br />

Power optimization is not permitted to run while SO3 optimization is tuning the feed rate. If power<br />

optimization is running, it will abort back to the first step and remain there until the SO3<br />

optimization module concludes the tuning process. When power optimization is re-enabled, it will<br />

start the program at the first step and proceed through the program at its normal rate. The<br />

controls selected in the SO3 optimization module for power monitoring will not have their power<br />

levels adjusted by power optimization while the S03 optimization module is running.<br />

SO3 optimization actions will be logged to disk anytime SO3 optimization is turned on in POS.<br />

The log will be the traditional file per day per point format. Each log entry contains the time and<br />

date stamp, SO3 enable input, PPM input, opacity (rolling avg.), load (rolling avg.) and power<br />

reading (rolling avg.). Each log entry will also contain text describing the action it has performed.<br />

The log interval will be the same as the “Wait Time” setting.<br />

When a user turns off SO3 optimization, POS will restore the SO3 PPM to the default feedrate.<br />

The PPM Graph displays a trend graph of the PPM of Sulfur fed into the system over time.<br />

The Opacity Graph displays a trend of Opacity over time.<br />

The Power Graph displays a trend of the Power Parameter selected in the <strong>System</strong> Settings<br />

Window.<br />

Set Axis<br />

The Set Axis button opens the Set Axis window. To change the X-Axis Scaling,<br />

click on the corresponding radio button to display 1 Day, 3 Days, 1 Week, or 3<br />

Weeks of data at a time.<br />

Print Charts<br />

The Print Charts button will open up a Print Preview window that will allow you to<br />

print the PPM, Opacity, and Power graphs displayed on the screen.<br />

Set X-Axis Window<br />

When SO3 <strong>Optimization</strong> is enabled, the Start button can be used to begin the optimization process.<br />

The window displays whether SO3 <strong>Optimization</strong> is enabled, the Default PPM, and the Optimized<br />

PPM. Pressing the Configure button opens the Configuration Window.<br />