Precipitator Optimization System User Manual - Neundorfer, Inc.
Precipitator Optimization System User Manual - Neundorfer, Inc.
Precipitator Optimization System User Manual - Neundorfer, Inc.
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>Precipitator</strong> <strong>Optimization</strong> <strong>System</strong> 7<br />
<strong>User</strong> <strong>Manual</strong><br />
Rapping Sequence<br />
This is where the device rapping order is set for selected field. The scroll list displays the<br />
rappers’ names in order of rapping sequence. Rappers can be added, inserted and deleted. To<br />
delete a single rapper select the rapper by clicking on its sequence number and pressing the<br />
Remove button. You can insert rappers into the sequence by selecting the location to insert it by<br />
clicking on the sequence number and pressing the Screen Pick (Insert at #) button. Change<br />
which field sequence you are viewing by clicking on the field buttons across the top of the page.<br />
Buttons with bold text have rappers in their sequence.<br />
Select the Dual Rapping field to allow the controller to energize two rappers in unison.<br />
Select the POR Enable field to enable the Power Off Rapping output for that rapper. The<br />
MicroRap will send out a POR signal to the MVC according to the POR Lead Time parameter.<br />
Use the Rapper On Time drop down list to set the on time for impact rappers in half-cycles and<br />
in seconds for vibrators.<br />
Use the Intensity drop down list to set the conduction angle of the phased-fired outputs.<br />
Click the Select All button before making any changes to have your changes apply to all rappers<br />
in the sequence for the selected field.<br />
Copyright © 2007 <strong>Neundorfer</strong>, <strong>Inc</strong>orporated<br />
Specifications and Features subject to change without notice<br />
08/01/07<br />
41