<strong>Precipitator</strong> <strong>Optimization</strong> <strong>System</strong> 7<br />

<strong>User</strong> <strong>Manual</strong><br />

When the start up / shut down module is running POS will not allow performance optimization, VI<br />

curves or SO3 optimization programs to run. If those modules are running when the start up /<br />

shut down mode is started, POS displays a message window that informs the user that these<br />

modules will be stopped. This window will give the users the option to continue start up / shut<br />

down or cancel. If the user tries to start those modules while in start up / shut down mode, POS<br />

will display a window informing the user that they can not run while in start up / shut down mode.<br />

Control Box<br />

Pressing the Start button begins selected program.<br />

Pressing the Stop button turns off the selected program. When stopping a program prior to<br />

completion, users will have the option of leaving the controls at their current set points, going to<br />

full power or turning the controls off.<br />

The Type box displays the type of program, start up or shut down, that you have selected in the<br />

drop list.<br />

The Step display shows the current program step number.<br />

The Setpoint display shows the current voltage control operating levels for the controls<br />

contained in the current step.<br />

Copyright © 2007 <strong>Neundorfer</strong>, <strong>Inc</strong>orporated<br />

Specifications and Features subject to change without notice<br />

08/01/07<br />

73