<strong>Precipitator</strong> <strong>Optimization</strong> <strong>System</strong> 7<br />
<strong>User</strong> <strong>Manual</strong><br />
or precipitator power levels that will cause optimization to abort to 100% power and start the<br />
process over or cause optimization to step back one step in the program before proceeding<br />
further. These limits and others are defined in the configuration portion of the manual.<br />
Auto <strong>Optimization</strong> suspension function provides an auxiliary input to optimization that will reset<br />
voltage controls to full power when the signal is present. POS will remember the program step it<br />
was executing when the signal was applied. When the signal is removed, POS will step through<br />
the optimization program at an accelerated rate until it reaches its previous location in the<br />
optimization program. When it reaches the previous location POS will revert to its default step<br />
time. The accelerated step time is user configurable and a parameter in optimization properties.<br />
If POS has to step back three times on a single program step when it is executing the<br />
optimization program at an accelerated rate, POS will revert to the default step time.<br />
Starting/Stopping Performance <strong>Optimization</strong><br />
<strong>Optimization</strong> Controls<br />
Pressing the On button turns on selected optimization program and optimization begins.<br />
Pressing the Off button turns off optimization program and voltage controls go to full power.<br />
The Program drop list allows the user to select what optimization program to run.<br />
The Status field contains information regarding the operation of optimization. Messages such as<br />
current step, optimization started, stopped, step back, step number, last step and aborted, among<br />
others, will be displayed here.<br />
The Time Left displays the time that is remaining in the current program step.<br />