6 Commentary on the Prescriptive Method for One and Two Family Dwellings - 2004<br />
The floor joist spans in the Prescriptive Method were derived assuming bearing stiffeners (also<br />
called transverse or web stiffeners) are located at all support or bearing point locations. Ceiling<br />
joist span tables were developed for two cases, 1) assuming bearing stiffeners are located at all<br />
support or bearing point locations and 2) bearing stiffeners are not installed at support or bearing<br />
point locations. Where specified, bearing stiffeners are to be a minimum of 43 mil (1.09 mm) track<br />
section or 33 mil (0.84 mm) C-shaped member.<br />
B3 Clip Angles<br />
All clip angle dimensions prescribed are shown as minimums. Clip angles that are of a<br />
greater base steel thickness or have greater overall dimensions, or both, are permitted to be<br />
used.