Commentary on the Prescriptive Method for One and Two Family Dwellings - 2004 43<br />

4’ 4’-2”<br />

Trimmer Joist<br />

8’<br />

6’<br />

40 psf Live Load<br />

14’-2”<br />

The maximum joist span per Table D3-1 of the Prescriptive Method is 14’-2”.<br />

The factored nominal flexural strength of the header joist is calculated using the AISIWIN<br />

computer program:<br />

ΦM 1 = 3,501 ft-lb<br />

ΦM 2 = 5,332 ft-lb<br />

(for 800T125-68)<br />

(for 800S162-68)<br />

Since the opening width is 8 feet, Section D-7 and Figure D7-2 of the Prescriptive Method<br />

require the trimmer joist to be fabricated from two joists and a track.<br />

ΦM T = 2(5,332) + 3,501 = 14,165 ft-lb<br />

The loading on the trimmer joist is as shown below. All loads are factored loads.<br />

608 lb<br />

630 lb<br />

152 lb/ft<br />

76 lb/ft<br />

152 lb/ft<br />

4’<br />

6’ 4.1’<br />

R1<br />

R2