Commentary on the Prescriptive Method for One and Two Family Dwellings - 2004 79<br />

E12.3 Length of Shear Panel (End Walls)<br />

P = 3,260/2 panels = 1,630 lb per shear wall<br />

Per Table 2211.1(1) of IBC 2000:<br />

V n = 910/2.5 = 364 lb with 6” fastener spacing.<br />

Length of shear panel required = 1,630/364 = 4.48 ft/shear wall<br />

4’<br />

12<br />

3<br />

9’<br />

Slab on Grade Foundation<br />

H<br />

H<br />

H<br />

H<br />

4’ 4’<br />

H<br />

5’ 5’<br />

H<br />

Sidewall Elevation<br />

“H” indicates Hold Down<br />

Endwall Elevation<br />

Verify the above design with the requirements of the Prescriptive Method:<br />

Range of allowable side wall lengths of one-story slab-on-grade<br />

(Table E13.1)<br />

Minimum = 14 feet/1.21 = 11.57’ (adjusted for Exposure Category B)<br />

Maximum = 60 feet/1.21 = 66.11 (adjusted for Exposure Category B)<br />

Required minimum length of full height sheathing on side walls (Type I):<br />

Minimum = 7’(1.13) = 7.91 feet (6” fastener spacing)<br />

(Table E13.3)<br />

Required minimum length of full height sheathing on side walls (Type I):<br />

Minimum sheathing length = 8’(1.13)(1/1.21)(0.8)<br />

= 5.23 feet (6” fastener spacing) (Table E13.4)<br />

(1.21 adjustment factor for Exp. B; 1.13 adjustment factor for 9’ walls; 0.8<br />

adjustment factor for mean roof height < 15’)<br />

Use (2) 4’ long shear walls with 7/16” OSB fastened with No. 8 screws at 6” o.c. at edges.<br />

Required minimum length of full height sheathing on end walls (Type I):