42 Commentary on the Prescriptive Method for One and Two Family Dwellings - 2004<br />

D2 Header Joist Design<br />

Check the adequacy of a 550S162-33 (33 ksi steel) header joist for a 6-foot floor opening<br />

width. The joists are spaced at 12” on center. The floor live load is 30 psf.<br />

6’<br />

30 psf Live Load 6’<br />

11’-7”<br />

Header<br />

Joist<br />

The maximum joist span per Table D3.1 of the Prescriptive Method is 11’-7”.<br />

The load on the header joist is calculated as follows:<br />

[ 1.2(10) + 1.6(30)](11.6' )<br />

W T =<br />

= 348 plf<br />

2<br />

2<br />

M =<br />

348(6)<br />

= 1,566 ft-lb<br />

8<br />

The factored nominal flexural strength of the header joist is calculated using the AISIWIN<br />

computer program. The header joist is fabricated from a joist nested in a track (550T125-33) as<br />

per Detail D7-1 of the Prescriptive Method.<br />

ΦM 1 = 783.65 ft-lb<br />

(for 550T125-33)<br />

ΦM 2 = 1,099.57 ft-lb (for 550S162-33)<br />

ΦM T = 783.65 ft-lb + 1,099.57 ft-lb = 1,883.22 ft-lb<br />

M/ΦM T = 1,566/1,883.22 = 0.83 < 1.0<br />

ok<br />

Note that the above calculation assumes that both header joists size and material are the<br />

same and hence posses similar stiffness. In most residential application this assumption is valid.<br />

However, in cases where header joist materials and/or sizes are different, stiffness calculations<br />

must be done and the appropriate load should be applied to each header joist (i.e., C-shape<br />

section and track section).<br />

D3 Trimmer Joist Design<br />

Check the adequacy of an 800S162-68 trimmer joist for an 8-foot wide by 6-foot long<br />

opening. The joists are spaced at 24” on center and the floor live load is 40 psf.