72 Commentary on the Prescriptive Method for One and Two Family Dwellings - 2004<br />

Hold Downs Required at Shear Wall Ends<br />

Single Shear Wall: T u = 3,730 lbs T ASD = 2,710 lb<br />

Aligning Shear Walls: T u = 6,910 lbs T ASD = 4,940 lb<br />

Using Simpson’s S/HTT-14 Hold Down with 5/8” diameter bolt for single shear wall:<br />

T allow = 5,260 lbs<br />

T allow = 3,950 lbs (without 1/3 increase for wind/seismic)<br />

T allow > T ASD = 2,710 lb<br />

Using Simpson’s S/HD8 Hold Down with 5/8” diameter bolt for aligning shear wall:<br />

T allow = 7,920 lbs<br />

T allow = 5,940 lbs (without 1/3 increase for wind/seismic)<br />

T allow > T ASD = 4,940 lb<br />

E11.5 Required Sheathing (End Walls)<br />

End wall shear walls use 7/16” OSB fastened with No. 8 screws at 6” at panel edges and<br />

12” at intermediate supports. Per previous calculations, L Required at 2 nd floor = 12.6’; and<br />

L Required at 1 st floor = 17.45’.<br />

Try Type II walls (perforated shear wall):<br />

Determine percentage of fully sheathed wall @ 2 nd floor = (5+12+5)/30 = 0.73 = 73.3%<br />

@ 1 st floor = (5+8+8)/30 = 0.70 = 70%<br />

Maximum unrestrained opening at 1 st and 2 nd floor = 7’, with wall fully sheathed above<br />

and below.<br />

Interpolate for length adjustment factor for both “percent fully sheathed wall” and<br />

“Maximum unrestrained opening”:<br />

At 2 nd Floor:<br />

% Fully Sheathed 6.75’ 7’ 7.5’<br />

60 1.28 1.32<br />

73.3 1.176 1.182 1.203<br />

80 1.12 1.14<br />

Therefore, the required length of fully sheathed (Type II) wall = (1.182)(12.60’) = 14.89’<br />

14.89’ < 22’ ok<br />

At 1 st Floor:<br />

% Fully Sheathed 6.75’ 7’ 7.5’<br />

60 1.28 1.293 1.32<br />

70 1.2 1.21 1.23<br />

80 1.12 1.127 1.14<br />

Therefore, the required length of fully sheathed (Type II) wall = (1.21)(17.45’) = 21.11’