Commentary on the Prescriptive Method for One and Two Family Dwellings - 2004 39<br />

D. FLOOR FRAMING <strong>DESIGN</strong> EXAMPLES<br />

D1 Floor Joist Design<br />

Calculate the allowable span for a 1000S162-54 single span joist spaced at 24” on center,<br />

supporting a live load of 40 psf plus a dead load of 10 psf, using the provisions of the AISI<br />

Specification (AISI, 1999). The compression flange of the joist is laterally restrained with the<br />

application of floor sheathing.<br />

D1.1 Shear Capacity<br />

Using the AISIWIN (Version 4.0) computer program, the nominal shear capacity is 2,408<br />

lb for a joist with no holes. (AISIWIN is available from DEVCO Software, Inc., Corvallis,<br />

OR.). The above shear capacity is verified below using Section C3.2 of the Specification.<br />

a = 2.5” (hole depth across web)<br />

Non-circular holes – 4” long<br />

F y = 33 ksi<br />

b = 24” (hole spacing)<br />

t = 0.0566” (thickness)<br />

R = 0.108” (inside bend radius)<br />

h = 10 - 2(0.0566 + 0.108) = 9.671”<br />

h/t = 9.671 / 0.0566 = 170.87 < 200<br />

ok<br />

Ek<br />

v<br />

0 .96 =<br />

F<br />

y<br />

0.96<br />

29,500x5.34<br />

33<br />

= 66.33<br />

Ek<br />

v<br />

1 .415 =<br />

F<br />

y<br />

1.415<br />

29,500x5.34<br />

33<br />

= 97.76<br />

where k v = 5.34 for unreinforced webs<br />

Ekv<br />

h/t = 170.87 > 1 .415 V n = 0.905 Ek v t 3 /h<br />

F<br />

V n =<br />

3<br />

0.905(29,500,000)(5.34)(0.0566)<br />

9.671<br />

y<br />

= 2,673 lb (web with no holes)<br />

Φ v V n = 2,673 x 0.90 = 2,406 lbs<br />

(web with no holes)<br />

Calculate the reduction in the nominal shear capacity due to the presence of punchouts<br />

using Section C3.2.2 of the AISI Specification.<br />

Check applicability of Section C3.2.2:<br />

d 0 /h = 2.5/9.67 = 0.258 < 0.7 ok<br />

h/t = 170.87 < 200 ok<br />

Holes centered at mid-depth of the web ok<br />

Clear distance between holes ≥ 18” ok<br />

Circular hole diameter ≤ 6” ok<br />

Non-circular holes, hole depth (d 0 ) = 2.5” ≤ 2.5” and b = 4” ≤ 4.5”<br />

ok