Commentary on the Prescriptive Method for One and Two Family Dwellings - 2004 67<br />

End wall roof area = (6/12)(15’)(15’) – 11.25 = 101 ft 2<br />

Side wall corner area = (4’+8’)(6’) = 72 ft 2<br />

Side wall area = (4’+8’)(50’) – 72 = 528 ft 2<br />

Side wall roof corner area = (1/2)(7.5)(6)(2) = 45 ft 2<br />

Side wall roof area = (7.5’)(50’) – 45 = 330 ft 2<br />

Building aspect ratio = 50/30 = 1.67<br />

Design shear at each side wall<br />

= [72 ft 2 (22.2 psf)+288 ft 2 (14.7psf)+11.25 ft 2 (22.2 psf)+101 ft 2 (14.7 psf)](1.6)/2 = 5,954 lb<br />

Design shear at each end wall<br />

= [72 ft 2 (27 psf) + (528 ft 2 (20.1psf) + 22.5 ft 2 (3.8 psf) + 330 ft 2 (3.3psf)](1.6)/2 = 10,985 lb<br />

E10.2 Required Sheathing (First Floor Walls)<br />

10,985<br />

Each end wall: = 21.95 ft<br />

910(0.55)<br />

This equates to 73% of end wall length.<br />

5,954<br />

Each side wall: = 11.90 ft<br />

910(0.55)<br />

This equates to 24% of side wall length.<br />

E11 Shear Wall Design (High Seismic Area)<br />

Design the lateral force resisting system for the example building shown below. Use Type I<br />

braced wall for the side walls and Type II braced walls for the end walls.<br />

E11.1 Design Assumptions<br />

Building Width = 30’<br />

Building Length = 50’<br />

Roof Slope = 6:12<br />

Seismic Design Category = D2<br />

Roof Dead Load = 15 psf<br />

Exterior Wall Dead Load = 7 psf<br />

Ground Snow Load = 25 psf<br />

Slab-on-grade foundation<br />

Interior Wall Dead Load = 5 psf<br />

Overhang = 2 ft<br />

Studs: 350S162-33<br />

Stud Spacing = 16” on center<br />

E11.2 Design Loads<br />

Roof Dead Load = 15 psf<br />

Floor Dead Load = 10 psf<br />

Exterior Wall Dead Loads = 7 psf<br />

Interior Walls Dead Load = 5 psf<br />

Floor area = (50’)(30’) = 1500 ft 2<br />

Roof area = [50’ + 2(2)][30’ + 4’] = 1836 ft 2 . (2’ overhangs)