80 Heat loss calculations<br />

2. The following materials are being considered for the internal skin of a cavity wall:<br />

(a)<br />

(b)<br />

(c)<br />

(d)<br />

(e)<br />

(f)<br />

105 mm brickwork;<br />

200 mm heavyweight concrete block;<br />

150 mm lightweight concrete block;<br />

75 mm expanded polystyrene slab;<br />

100 mm mineral fibre slab and 15 mm plasterboard;<br />

40 mm glass fibre slab, 150 mm lightweight concrete block and 15 mm lightweight<br />

plaster.<br />

Compare their thermal resistances and comment upon their suitability for a residence.<br />

3. Calculate the thermal transmittances of the following:<br />

(a)<br />

(b)<br />

(c)<br />

(d)<br />

(e)<br />

(f)<br />

(g)<br />

single-glazed window, severe exposure;<br />

double-glazed window, sheltered exposure;<br />

220 mm brick wall and 13 mm lightweight plaster;<br />

220 mm brick wall, 50 mm glass fibre quilt and 10 mm plasterboard;<br />

105 mm brick wall, 10 mm air space, 40 mm glass fibre slab and 100 mm lightweight<br />

concrete block;<br />

40 ◦ pitched roof, 10 mm tile, roofing felt and 10 mm flat plaster ceiling with 100 mm<br />

glass fibre quilt laid between the joists;<br />

19 mm asphalt flat roof, 13 mm fibreboard, 25 mm air space, 100 mm mineral wool<br />

quilt and 10 mm plasterboard.<br />

All exposures are normal unless otherwise specified.<br />

4. A lounge 7 m long × 4 m wide × 2.8 m high is maintained at a resultant temperature of<br />

21 ◦ C and has 1.5 air changes/h of outside air at −2 ◦ C. There are two double-glazed woodframed<br />

windows of dimensions 2 m × 1.5 m and an aluminium framed double-glazed door<br />

of dimensions 1 m × 2 m. Exposure is normal. One long and one short wall are external<br />

and constructed of 105 mm brick, 10 mm air space, 40 mm polyurethane board,<br />

150 mm lightweight concrete block and 13 mm lightweight plaster. The internal walls are<br />

of 100 mm lightweight concrete block and are plastered. There is a solid ground floor with<br />

edge insulation. The roof has a thermal transmittance of 0.34 W/m 2 K. Adjacent rooms are<br />

at a resultant temperature of 18 ◦ C. Calculate the steady-state heat loss from the room for<br />

a convective heating system.<br />

5. A single-storey community building of dimensions 20 m × 15 m × 3 m high has<br />

low-temperature hot-water radiant panel heaters. There are 10 windows of dimensions<br />

2.5 m × 2 m. Natural infiltration amounts to 1 air change/h. Internal and external design<br />

temperatures are 20 ◦ C and −1 ◦ C. Thermal transmittances are as follows: walls, 0.6 W/m 2 K;<br />

windows, 5.3 W/m 2 K; floor, 0.5 W/m 2 K; roof, 0.4 W/m 2 K. Calculate the steady-state<br />

heat loss.<br />

6. Calculate the environmental temperature produced in an unheated room within an occupied<br />

building, using the following information: room dimensions, 5 m × 4m× 2.6 m high; a<br />

window of dimensions 2.5 m × 1.25 m in one long external wall; 0.5 air changes/h; external<br />

air temperature, 3 ◦ C; solid ground floor; surrounding rooms are all at an environmental<br />

temperature of 20 ◦ C. The thermal transmittances are as follows: external wall, 1 W/m 2 K;<br />

window, 5.3 W/m 2 K; floor, 0.7 W/m 2 K; internal walls, 1.2 W/m 2 K; ceiling, 1 W/m 2 K.<br />

Assume that the room environmental temperature is equal to the air temperature.<br />

7. A single-storey factory is allowed to have 35% of its wall area as single glazing and 20% of its<br />

roof area as single-glazed roof-lights. Wall and roof U values are not to exceed 0.6 W/m 2 K.<br />