300 Electrical installations<br />

For1mm 2 cable:<br />

l =<br />

9.6 × 103<br />

12.5 × 44 m = 17.5 m<br />

For 1.5 mm 2 cable:<br />

l =<br />

9.6 × 103<br />

12.5 × 29 m = 26.5 m<br />

For 2.5 mm 2 cable:<br />

l =<br />

9.6 × 103<br />

12.8 × 18 m = 42.7 m<br />

Construction site distribution<br />

A list is made of all electrical equipment to be used on site in order to assess the maximum<br />

demand kilovolt-amperes and cable current rating required. An estimate of the cost of electricity<br />

for running the site may also be made.<br />

EXAMPLE 13.7<br />

A building site is to have the following electrical equipment available for use:<br />

(a) tower crane, electric motors totalling 75 kW at 415 V;<br />

(b) sump pump, 5 kW at 240 V;<br />

(c) 60 tungsten lamps of 100 W each at 240 V;<br />

(d) 12 flood lamps of 400 W each at 240 V;<br />

(e) 20 hand tools of 400 W at 110 V.<br />

1. Find the total kilovolt-amperes to be supplied to the site if the power factor of all<br />

rotary equipment is 0.8.<br />

2. Find the electrical current rating for the incoming supply cable to the site.<br />

3. Estimate the cost of electricity consumed on the site during a 12-month contract.<br />

For rotating machinery:<br />

power, VA =<br />

For single-phase current:<br />

useful power W<br />

PF<br />

= W 0.8<br />

and, kVA =<br />

kW<br />

PF<br />

line current = VA V A<br />

= kVA<br />

kV A