Built environment 11<br />

Atmospheric vapour pressure p is that part of the barometric pressure produced by the water<br />

vapour in humid air. Standard atmospheric pressure at sea level is 1013.25 mb (millibars) and this<br />

comprises about 993.0 mb from the weight of dry gases and 20.25 mb from the water vapour,<br />

depending on the values of barometric pressure, air temperature and humidity.<br />

The comfort equation balances to zero when heat transfers between the body and surroundings<br />

are stable. This is the thermally neutral condition when there are no feelings of discomfort.<br />

It is unlikely to be satisfied for a group of people, and a comfort zone is used to specify the range<br />

of acceptable levels for the majority.<br />

Comfort measurement<br />

Figure 1.1 shows the percentage of people dissatisfied (PPD) and predicted mean vote (PMV)<br />

that are used for the assessment of indoor thermal environments, from Fanger. The chart<br />

demonstrates that dissatisfaction among less than one-third of the occupants is achieved<br />

in indoor environments within the slightly cool to slightly warm categories. Personal variation<br />

in clothing, sedentary position and control over the microclimate being the final control<br />

mechanism.<br />

A thermal comfort analogue computer may be used to make this assessment with an<br />

ellipsoidal-shaped sensor that is around the size of a straight banana. This shape has the same<br />

mathematical relationship between its heat loss by radiation and convection as the human body.<br />

To obtain values of temperature, velocity, carbon dioxide and humidity in the atmosphere,<br />

each is measured separately as 0–10 V or 0–20 mA analogue signals, converted into digital bytes<br />

with an analogue-to-digital converter and then stored in a data logger in random access memory.<br />

Numerous readings are easily retained in memory for later access through a desktop or portable<br />

computer. Lists of data numbers and their time of occurrence can be stored on hard and floppy<br />

disks for processing with dedicated software or any spreadsheet program. Graphical output can<br />

show the history of the recorded temperature, or other variable, during a period of time. Such<br />

graphs are termed trends. The software can be programmed to take readings at, say, intervals of<br />

2 s or longer, or only whenever a significant change takes place. Figure 1.2 shows the schematic<br />

arrangement of a data-logging system with a trend display of room air temperature. Figure 1.3<br />

is a photograph of a portable data-logging cart created to assess existing building conditions.<br />

100<br />

Predicted percentage of<br />

dissatisfied people<br />

80<br />

60<br />

40<br />

20<br />

Comfort<br />

zone<br />

–3<br />

Cold<br />

–2<br />

Cool<br />

1.1 PPD versus PMV.<br />

–1<br />

Slightly<br />

cool<br />

0<br />

Neutral<br />

1<br />

Slightly<br />

warm<br />

Predicted mean vote<br />

2<br />

Warm<br />

3<br />

Hot