Ventilation and air conditioning 169<br />

43. Which is not correct for natural ventilation in the UK?<br />

1. Must generate at least 4 air changes/h.<br />

2. Often associated with low-energy buildings.<br />

3. Original means of ventilating pre-1950’s traditional brick buildings.<br />

4. Always justifiable in this climate.<br />

5. Often only provides up to 3 air changes/h.<br />

44. What is meant by hybrid ventilation?<br />

1. System has latest technology in computer control.<br />

2. Only works in tall buildings.<br />

3. Combines active control of natural ventilation with mechanical air movement<br />

systems.<br />

4. Unnatural combination of mechanical systems with manually operated ventilators.<br />

5. Combination of systems invented by Hyme Bridowski in 1935.<br />

45. What drives the fan in a large air-handling unit?<br />

1. Diesel engine prime mover.<br />

2. Three-phase electric motor.<br />

3. Single-phase synchronous alternating current motor.<br />

4. 1000 V AC motor.<br />

5. 240 V AC motor.<br />

46. Which is a small fan drive motor, such as in a FCU?<br />

1. DC variable-speed motor as they are lowest cost.<br />

2. 415 V AC motor if they require around 850 W power output.<br />

3. Three-phase for any size as this is the most energy-efficient type.<br />

4. 240 V, three-phase synchronous electric motor.<br />

5. 240 V, single-phase direct drive motor.<br />

47. AHU chilled-water flow control is by:<br />

1. Modulating damper.<br />

2. Electronic control system.<br />

3. Modulating water flow valve.<br />

4. Manually set only once by the commissioning engineer.<br />

5. All valves remain fully open to maximize available cooling during hot weather.<br />

48. An office 15.0 m × 7.0 m × 2.8 m has 11.0 air changes/h from air supplied through a duct<br />

where it flows at a velocity of 8.5 m/s. Which two answers are correct?<br />

1. Supply air flow rate is 1.20 m 3 /s.<br />

2. Supply air flow rate is 750.0 l/s.<br />

3. Supply air flow rate is 0.9 m 3 /s.<br />

4. Duct dimensions are 325 mm × 325 mm.<br />

5. Duct dimensions are 650 mm × 325 mm.<br />

49. A retail shop 22.0 m × 6.5 m × 3.5 m has 7.5 air changes/h from air supplied through a duct<br />

where it flows at a velocity of 9.5 m/s. Which two answers are correct?<br />

1. Supply air flow rate is 0.085 m 3 /s.<br />

2. Supply air flow rate is 1043 l/s.