Electrical installations 307<br />

Electrical distribution within a building<br />

The incoming cable, residual current device and meter are the property of the electricity supply<br />

authority. Underground cables are at a depth of 760 mm under roads, and enter the building<br />

through a large radius service duct of 100 mm internal diameter. A drainpipe can be used for this<br />

purpose, laid through the foundations and rising directly to the meter compartment. External<br />

meter compartments can be used. The meter should not be exposed to damp or hot conditions<br />

and the electricity supply authority’s advice should be sought. Figure 13.9 shows a distribution<br />

system for a dwelling.<br />

Each circuit has a fuse or circuit-breaker and the fused distribution board connects the neutral<br />

and earth protective conductors to the supply cable. Appliances have a cartridge fuse at their<br />

connecting plug. Three-phase distribution in a large building is shown in Fig. 13.10. Switches are<br />

used to enable separation of individual circuits as well as appliances. A fuse or circuit-breaker is<br />

always fitted on the live line so that the incoming current is disconnected.<br />

Power socket outlets are fitted into a ring circuit as shown in Fig. 13.11. Care must be taken<br />

not to overload the circuit by connecting appliances whose total current consumption would<br />

exceed the 30 A limit, particularly in kitchens.<br />

Types of cable used in distribution systems are as follows.<br />

PVC-insulated and -sheathed<br />

PVC-insulated and -sheathed cables consist of copper conductors of multi-stranded or solid wire<br />

having sizes from 1 to 16 mm 2 cross-sectional area. Single-, twin- or three-core cables, with or<br />

without earth wires, are used. They are among the cheapest cables available and can be pulled<br />

through conduits, trunking or holes bored in floor joists. Such holes are drilled 50 mm below the<br />

Lighting<br />

Consumers main<br />

switch and residual<br />

current device,<br />

30 mA trip,<br />

60 A current capacity<br />

Power points<br />

Immersion heater<br />

Cooker<br />

Meter<br />

N L<br />

LN<br />

60 A residual current<br />

device, sealed by<br />

electricity supply authority<br />

LN E<br />

Incoming<br />

electrical<br />

supply<br />

cable<br />

LN<br />

Gas<br />

service<br />

Water<br />

main<br />

5A<br />

L<br />

30 A 15 A 30 A<br />

N<br />

E<br />

<strong>Services</strong> bonded to<br />

electrical earth<br />

13.9 Domestic electricity distribution.<br />

NE<br />

Fused<br />

distribution<br />

board<br />

Earth terminal<br />

Neutral terminal