16.06.2016 Views

Building Services Engineering 5th Edition Handbook

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

144 Ventilation and air conditioning<br />

The mass flow balance for the junction is:<br />

mass flow of stream 1 + mass flow of stream 2 = mixed mass flow<br />

or,<br />

Q 1 ρ 1 + Q 2 = Qρ<br />

The enthalpy balance, taking the specific heat capacity as constant, is:<br />

Q 1 t 1 + Q 2 t 2 = Qt<br />

Dividing through by Q gives,<br />

Q 1<br />

Q t 1 + Q 2<br />

Q t 2 = t<br />

The mixed air temperature and moisture content lie on the straight line connecting the two entry<br />

conditions and can be found by the volume flow rate proportions as indicated by the equation.<br />

Humidification<br />

In winter, incoming fresh air with a low moisture content can be humidified by steam injection,<br />

banks of water sprays, evaporation from a heated water tank or a spinning disc atomizer. A<br />

preheater low-pressure hot-water coil usually precedes the humidifier to increase the waterholding<br />

capacity of the air. This also offsets the reduction in temperature of the air owing to<br />

transference of some of its sensible heat into latent energy, which is needed for the evaporation<br />

process. Figure 5.8 shows such an arrangement.<br />

A temperature sensor in the humidified air is used as a dew-point control by modulating<br />

the preheater power to produce air at a consistent moisture content throughout the winter. For<br />

comfort air conditioning, the room percentage saturation will be 50% ± 10%. This permits a<br />

wide range of humidifier performance characteristics.<br />

The humidification process often follows a line of constant wet-bulb temperature. The water<br />

spray temperature is varied to alter the slope of the line on the psychrometric chart. A complete<br />

psychrometric cycle for a single-duct system during winter operation is shown in Fig. 5.9. The<br />

preheating and humidification stages have been omitted, as close humidity control is deemed<br />

not to be needed in this case. A typical summer cycle is shown in Fig. 5.10.<br />

Some reheating of the cooled and dehumidified air will be necessary because of practical<br />

limitations of cooling coil design. Part of the boiler plant remains operational during the summer.<br />

Reheating can be avoided by using a cooling coil bypass which mixes air M and air C to produce the<br />

correct supply condition. Heating and refrigeration plant capacities are found from the enthalpy<br />

changes and specific volume, read from the chart, and the air volume flow rate:<br />

heat transfer rate = Q m3<br />

s<br />

× kg<br />

v s m 3 × (SE 1 − SE 2 ) kJ<br />

kg × kWs<br />

kJ

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!